adding refrigerant

Add refrigerant charge according to table below:
If you use a pipe longer than 5 m,
15 g of refrigerant R-410A must be added for each extra meter .
If you use a pipe shorter than 5 m,
The evacuating time is normal .
Refer to the Service Manual for further details .
• The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction on the compressor .
• Always contact the service center or a professional installation agency for product installation .
Charging the refrigerant under conditions of liquid by using a liquid pipe
R-410A is a mixed type of refrigerant . It is necessary for recharging under conditions of liquid . When recharging refrigerant from
the refrigerant cylinder to the equipment, follow the instructions below .
1. Before recharging, check whether the cylinder has a siphon or not.
There are two ways to recharge the refrigerant.
Cylinder with siphon
f Charge the refrigerant standing the cylinder
f
upright .
• If R-410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the
characteristics of the equipment vary .
• During the measuring operation of refrigerant quantity added use electronic scales .
If cylinder doesn't have syphon, upset it .
RAC BORACAY_EN_Eco-inverter IBIM_05124A-00.indd 47
Siphon
f Charge the refrigerant standing the cylinder
f
English-47
Cylinder without siphon
upright .