Panasonic WH-UD30BE5-1 Service Manual page 68

Air-to-water heatpump
Hide thumbs Also See for WH-UD30BE5-1:
Table of Contents

Advertisement

16.5.25. Indoor Water Outlet Temperature Sensor Abnormality (F45)
Malfunction Decision Conditions:
During startup and operation of heating, the temperatures detected by the indoor water outlet temperature sensor are used to
determine sensor error.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty sensor.
3. Faulty indoor unit PCB.
Abnormality Judgment:
Continue for 5 seconds.
68

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-ud24be5-1Wh-sd30be5-1Wh-sd24be5-1

Table of Contents