16.5.4. Water Flow Switch Abnormality (H62)
Malfunction Decision Conditions:
During operation of heating, the water flow detected by the indoor water flow switch is used to determine water flow error.
Malfunction Caused:
1. Faulty water pump.
2. Water leak in system.
3. Faulty connector connection.
4. Faulty water flow switch.
5. Faulty indoor unit PCB.
Abnormality Judgment:
Continue for 1 minute (but no judgment for 9 minutes after compressor startup/restart).
47