Panasonic WH-UD30BE5-1 Service Manual page 57

Air-to-water heatpump
Hide thumbs Also See for WH-UD30BE5-1:
Table of Contents

Advertisement

16.5.14. Compressor Overheating (F20)
Malfunction Decision Conditions:
During operation of heating, when temperature above 112°C is detected by the compressor tank temperature sensor.
Malfunction Caused:
1. Faulty compressor tank temperature sensor.
2. 2/3 way valve closed.
3. Refrigerant shortage (refrigerant leakage).
4. Clogged expansion valve or strainer.
5. Faulty outdoor unit PCB.
6. Faulty compressor.
Abnormality Judgment:
Continue 4 times in 30 minutes.
57