Terminal screw
Tightening torque N cm {kgf cm}
M4
M5
157~196 {16~20}
196~245 {20~25}
11.3.4.1. Wire Stripping and Connecting
Requirement
11.3.4.2. Connecting Requirement
• This equipment complies with IEC 61000-3-12 provided that
the short-circuit power S
UD24BE5-1: 961.61kW, UD30BE5-1: 961.61kW at the
interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is
connected only to a supply with a short circuit power S
greater
than
or
UD30BE5-1: 961.61kW.
• This equipment is intended for use only in premises having
service current capacity 100A per phase. Please liaise with
supply authority to ensure that the service current capacity
at the interface point is sufficient for the installation of the
equipment.
27
is greater than or equal to
sc
equal
to
UD24BE5-1:
sc
961.61kW,