Panasonic WH-UD30BE5-1 Service Manual page 58

Air-to-water heatpump
Hide thumbs Also See for WH-UD30BE5-1:
Table of Contents

Advertisement

16.5.15. IPM Overheating (F22)
Malfunction Decision Conditions:
During operation of heating, when temperature 95°C is detected by the outdoor IPM temperature sensor.
Malfunction Caused:
1. Faulty outdoor unit fan motor.
2. Faulty outdoor unit PCB.
Abnormality Judgment:
Continue 3 times in 30 minutes.
58

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wh-ud24be5-1Wh-sd30be5-1Wh-sd24be5-1