Safety Limit Checklist
The following checklists are designed to assist the service
technician in analysis. However, because there are many
possible external problems, do not limit your diagnosis to
only the items listed.
Safety Limit #1
Freeze time exceeds 60 minutes for 6 consecutive
freeze cycles.
Possible Cause Checklist
Improper Installation
Refer to "Installation and Visual Inspection Checklist"
on page 60
Water System
Water Level set too high (water escaping through
over flow tube)
Low water pressure (20 psig min.)
High water pressure (80 psig max.)
High water temperature (90°F/32.2°C max.)
Clogged water distribution tube
Dirty/defective float valve
Defective water pump
Electrical System
Ice thickness probe out of adjustment
Harvest cycle not initiated electrically
Compressor relay not energizing
Compressor electrically non-operational
High inlet air temperature (110°F/43.3°C max.)
Defective fan cycling control
Defective fan motor
Dirty condenser