Electrical Data - Tandem Compressor (X2) - AIREDALE LogiCool InRak Technical Manual

Hide thumbs Also See for LogiCool InRak:
Table of Contents

Advertisement

IT Cooling
Technical - Direct Expansion

Electrical Data - Tandem Compressor (X2)

Standard Condenser Match -
Unit Data Cooling only
Nominal Run Amps
Maximum Start Amps
Recommended Mains Fuse Size
Max Mains Incoming Cable Size
Mains Supply 50Hz (-0)
Mains Supply 60Hz (-1)
Control Circuit
Evaporator Fan - Motor - Per Fan
Motor Type
Quantity x Motor Size
Full Load Amps
Locked Rotor Amps
Compressor 1
Motor Size
Nominal Run Amps
Max Run Amps
Type of Start
Compressor 2
Motor Size
Nominal Run Amps
Locked Rotor Amps
Type of Start
Standard Condenser Match – AC Motor
Per Fan
Quantity x Motor Size (50Hz Supply)
Full Load Amps (50Hz Supply)
Quantity x Motor Size (60Hz Supply)
Full Load Amps (60Hz Supply)
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat
Number of Elements
Rating (Total)
Current Per Phase (50Hz Supply)
Current Per Phase (60Hz Supply)
Standard Condenser Match - EC Motor-
Per Fan
Mains Supply 50Hz (-0)
Mains Supply 60Hz (-1)
Quantity x Motor Size (50Hz Supply)
Full Load Amps (50Hz Supply)
Quantity x Motor Size (60Hz Supply)
Full Load Amps (60Hz Supply)
SCAF Condenser Match - Motor - Per
Fan
Quantity x Motor Size (50Hz Supply)
Full Load Amps (50Hz Supply)
Quantity x Motor Size (60Hz Supply)
Full Load Amps (60Hz Supply)
(1) Values given for unit variants at 11°C evaporating and 46°C condensing.
(2) Stated motor power is based on maximum electrical power absorbed.
(3) Values are per compressor.
(4) Values may change based on additional selections (i.e. Heating).
(5) Values based on Fuse size., May change based on unit selections.
LIR6042U-X240-0
CR65
(1)
A
27.9
A
89.3
(4)
A
50
(5)
mm²
16
V
V
VAC
EC
(2)
kW
4 x 0.5
A
2.2
A
N/A
(3)
kW
5.25
A
18.8
A
24.9
Soft Start
(3)
kW
4.28
A
6.2
A
60.0
Direct On Line
kW
2 x 0.6
A
2.6
kW
2 x 0.5
A
2.2
Variable
3
kW
10.5
A
15.2
A
16.0
V
V
kW
2 x 0.72
A
3.2
kW
2 x 0.77
A
3.3
kW
2 x 1.4
A
6.0
kW
2 x 1.75
A
7.8
InRak™ Technical Manual 7462807 V1.11.0_04_2016
LogiCool InRak™
LIR6042U-X250-0
CR80
29.4
89.3
50
16
400V / 3PH + N / 50Hz
380V / 3PH + N / 60Hz
24
EC
4 x 0.5
2.2
N/A
5.25
18.8
24.9
Soft Start
4.28
6.2
60.0
Direct On Line
3 x 0.6
2.6
3 x 0.5
2.2
Variable
3
10.5
15.2
16.0
230V / 1PH + N / 50Hz
220V / 1PH + N / 60Hz
3 x 0.72
3.2
3 x 0.77
3.3
3 x 1.4
6.0
3 x 1.75
7.8
31