To further protect your investment in Airedale products, we have introduced Airedale Service, who can provide full commissioning services, comprehensive maintenance packages and service cover 24 hours a day, 365 days a year (UK mainland). For a free quotation contact Airedale Service or your local Sales Engineer.
Chillers ULTIMA FREECOOL Contents GENERAL STATEMENT Safety WARRANTY GENERAL DESCRIPTION Unit Identification Standard Features Optional Extras - Energy Saving Optional Extras - General INSTALLATION DATA Dimensions Point Loading & Centre of Gravity Weights Unit Lifting Anti Vibration Mounting Positioning Water System Data...
CAUTION Service and maintenance of Airedale equipment should only be carried out by Technically trained competent personnel. CAUTION When working with any air conditioning units ensure that the electrical isolator is switched off prior to servicing or repair work and that there is no power to any part of the equipment.
Installation & Maintenance manual provided, during the Warranty Period. In the event of a problem being reported, Airedale will cover the full cost of rectification (excluding costs for any specialist access or lifting equipment) if warranty is valid under these conditions.
Example UFC200D-8 INTRODUCTION The Airedale range of Ultima FreeCool air cooled liquid chillers covers the cooling capacity range 200kW to 750kW in 39 model sizes incorporating Standard D, Quiet DQ and Super Quiet DSQ variations. Attention has been placed on maximising the unit’s cooling and energy performance while keeping the sound, vibration levels and footprint to an absolute minimum.
Page 7
Chillers ULTIMA FREECOOL General Description STANDARD FEATURES Refrigeration Each refrigeration circuit is supplied with the following: • Full operating charge of R407C • Liquid injection oil cooling circuit fitted to each compressor as standard with filter, sight glass, strainer and non-return valve •...
ULTIMA FREECOOL Chillers General Description OPTIONAL EXTRAS - ENERGY SAVING Power Factor Correction When applied to the motors of each compressor, the compressor power factor is controlled to a minimum operating value of 0.95 at the full operating capacity. This satisfies many supply authorities that may impose surcharges on equipment with power factor less than 0.95.
ULTIMA FREECOOL Chillers Installation Data UNIT LIFTING • Employ lifting specialists. • Local codes and regulations relating to the lifting of this type of equipment should be observed. • Use the appropriate spreader bars/lifting slings with the holes/lugs provided. Attach lifting chains to the 4 lifting lugs provided, each chain must be capable of •...
Page 13
CAUTION Do not connect any services until all anti vibration mounts have been fully adjusted. Airedale International Air Conditioning Ltd Leeds Road, Rawdon, Leeds. LS19 6JY England Tel: + 44 (0) 113 239 1000 Fax: + 44 (0) 113 250 7219...
Chillers ULTIMA FREECOOL Installation Data ANTI VIBRATION Locate and secure mount using bolting down holes provided in base plate. Ensure mounts are located in line with the chiller base. MOUNTING If applicable remove compressor enclosure covers to allow access to AV fixing CLS Type (Optional) points on the chiller base.
ULTIMA FREECOOL Chillers Installation Data POSITIONING The installation position should be selected with the following points in mind: • Position on a stable and even base, levelled to ensure that the compressor operates correctly. • Levelling should be to +/- 5mm •...
CAUTION The unit water connections are NOT designed to support external pipework, pipework should be supported during installation. CAUTION No liability for externally connected pipework will be regarded by Airedale International Air Conditioning Ltd. STANDARD RECOMMENDED INSTALLATION CAUTION The following installation recommendations should be adhered to. Failure to do this could invalidate the chiller warranty.
Page 17
To prevent air locking in the system it is advisable to fill the systems from the lowest point, ie drain point on pipework. Auto air vents are fitted, Airedale strongly recommends an auto pressurisation unit be fitted to the system.
Chillers ULTIMA FREECOOL Installation Data GLYCOL DATA CAUTION All free-cooling units should use minimum 20% glycol concentration. Ethylene Glycol Nominal Correction Factors Glycol in System / Freezing Point ºC 20% / -9°C 30% / -15°C 40% / -23°C Cooling Duty 1.00...
ULTIMA FREECOOL Chillers Installation Data ELECTRICAL DATA General • As standard the equipment is designed for 400V, 3 phase, 3 wire 50Hz and a separate permanent 230V, 1 phase, 50Hz supply, to all relevant IEE regulations, British standards and IEC requirements.
Page 20
Chillers ULTIMA FREECOOL Installation Data INTERCONNECTING WIRING No Pumps Mains incoming supply 400V/3PH/50Hz " " " " Separate Permanent Supply 230V/1PH/50Hz " " " External Trace Heating Connections 240V/500W max " (1)Evaporator Pump Interlock 24VAC " UFC200 – UFC750 Unit Remote On/Off 24VAC "...
Page 21
Motor Rating 0.70 0.70 0.70 0.70 0.70 OPTIONAL EXTRAS - Fitted to standard D models - for data on DQ & DSQ please refer to Airedale. Power Factor Correction Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Compressor Nominal...
Page 22
Motor Rating 0.70 0.70 0.70 0.70 0.70 OPTIONAL EXTRAS - Fitted to standard D models - for data on DQ & DSQ please refer to Airedale. Power Factor Correction Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Compressor Nominal...
Page 23
2.10 2.10 Motor Rating 0.70 0.70 0.70 OPTIONAL EXTRAS - Fitted to standard D models - for data on DQ & DSQ please refer to Airedale. Power Factor Correction Nominal Run Amps Maximum Start Amps Recommended Mains Fuse Compressor Nominal...
ULTIMA FREECOOL Controls CONTROL SCHEME Airedale recognises that all chiller applications are different but fall mainly into 2 application categories; Variable Supply Temperature and Constant Supply Temperature. FEATURES The onboard microprocessor has the capability of satisfying either control requirement as illustrated below.
ULTIMA FREECOOL Chillers Controls GENERAL microprocessor controller offers powerful analogue and digital control to meet a wide range of monitoring and control features including a real time clock and Industry standard communication port and network connections. The controller’s inbuilt display is used for viewing the unit operating status and making adjustments to control parameters and visual alarm by allowing the operator access to a series of display pages.
Time Zones The programme provides 3 On/Off periods per day, 7 days per week. The unit is factory set for continuous operation. Technical Support For further details, please contact Airedale. Chillers Installation & Maintenance Manual : 903-125 IM E 05/04/A...
ULTIMA FREECOOL Chillers Controls VIEWING UNIT OPERATING STATUS Status Menu Allows access to view operating status of Digital and Analogue Inputs and Outputs. Using the Navigation instructions, the following Sub-Menus shown in sequence can be accessed: Digital Inputs Analogue Inputs...
Chillers ULTIMA FREECOOL Controls ALARMS The controller logs and allows viewing of the last 100 conditions recorded in descending chronological order. 1 3 / 0 5 / 0 2 1 1 : 3 2 E v e n t n u m b e r...
Maximum Ambient Air DB °C Refer to Technical Manual - Performance Data Minimum Leaving Water Temperature °C +5°C Maximum Return Water Temperature °C +20°C For conditions outside those quoted, please refer to Airedale. MECHANICAL DATA Oil & Refrigerant Charges STANDARD D UFC200D-8 UFC225D-8...
Chillers ULTIMA FREECOOL Commissioning Data ELECTRICAL DATA CLIENTS INCOMING Compressor Start-Up SUPPLY 400/3/50 Information POWER FACTOR CORRECTION CLOSED TRANSITION START OPTIONAL EXTRA OPTIONAL EXTRA POWER POWER FACTOR FACTOR CORRECTION CORRECTION PRR1 CAPACITOR CAPACITOR PHASE COMPRESSOR ROTATION RELAY Starting Sequence (Star- Delta Starting) 5 Sec ±...
Page 33
ULTIMA FREECOOL Chillers Commissioning Data ELECTRICAL DATA Capacity Control The following staggered timings are recommended on compressor start-up: 100% 75 Sec ± 5 180 Sec ± 10 • 12% load (starting position) should be used only at start-up, never as a stage of capacity control.
GENERAL To be read in conjunction with the commissioning sheets provided, items highlighted should be recorded. CAUTION Please ensure all documents have been completed correctly and return to Airedale Service immediately to validate warranty. PRE COMMISSIONING CHECKLIST CAUTION ALL work MUST be carried out by Technically Trained competent personnel.
Page 35
ULTIMA FREECOOL Chillers Commissioning Procedure PRE COMMISSIONING CHECKLIST (CONT..) Waterflow • Drive the 3-way valve fully open by raising the return water temperature above the ambient and measure the pressure drop across the free cooling coils. Commissioning • Lower the return water temperature to below the ambient to close the valve fully.
Chillers ULTIMA FREECOOL Commissioning Procedure COMMISSIONING The following should be carried out with a load on the system, otherwise the unit is likely to short cycle. The following tests are to be carried out on 1 circuit at a time.
FABRIC Visually inspect the unit for general wear and tear, treat Rust should be inhibited, primed and touched up metalwork. with matching paint (available from Airedale or your Distributor). Visually inspect pipe and pipework insulation. Repair/rectify as necessary. Clean water strainer.
Chillers ULTIMA FREECOOL Maintenance GENERAL MAINTENANCE 6 MONTHS ACTION NOTES Repeat 3 month checks plus the following: SYSTEM Check evaporator trace heating and low ambient thermostat Remember to re-cap the Schraeder are set to activate at 4.0ºC. connections! 12 MONTHS...
Chillers Parts Identification SPARES For ease of identification when ordering spares or contacting Airedale about your unit, please quote the unit type, unit serial number and the date of manufacture, which can be found on the unit serial plate. A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on request.
Page 42
Chillers ULTIMA FREECOOL Parts Identification Pump Bus bar Chamber 3 phase Mains Incoming Evaporator Door Interlocking isolator Fan and Motor Assemblies Star Delta Contactors Free Cooling Condensing Coils Closed Transition Connection Compressor Feet/Resilient Pads Power Factor Correction Unloading Solenoid Valves...
Page 43
ULTIMA FREECOOL Chillers Notes: Chillers Installation & Maintenance Manual : 903-125 IM E 05/04/A...
Page 44
Chillers ULTIMA FREECOOL Notes: Chillers Installation & Maintenance Manual : 903-125 IM E 05/04/A...
Page 45
Head Office: Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY United Kingdom Tel: +44 (0) 113 239 1000 Fax: +44 (0) 113 250 7219 e-mail: enquiries@airedale.com website: www.airedale.com PART NO: ISSUE DATE 903-125 IM E 01/05/04...
Page 46
Airedale Departmental Contact Details: CUSTOMER SERVICES For further assistance, please e-mail: enquiries@airedale.com or telephone: Customer Services UK Sales Enquiries + 44 (0) 113 238 7789 uk.sales@airedale.com International Enquiries + 44 (0) 113 239 1000 enquiries@airedale.com Spares Hot Line + 44 (0) 113 238 7878 spares@airedale.com...