AIREDALE SmartCool SN Series Technical Manual

Chilled water

Advertisement

SmartCool™ Downflow
6 to 200kW
SN, SR and SD
SmartCool Chilled Water
Technical Manual

Advertisement

Table of Contents
loading

Summary of Contents for AIREDALE SmartCool SN Series

  • Page 1 SmartCool™ Downflow 6 to 200kW SN, SR and SD SmartCool Chilled Water Technical Manual...
  • Page 2 Airedale Ltd. endeavours to ensure that the information in this document is correct and fairly stated, but none of the statements are to be relied upon as a statement or representation of fact. Airedale Ltd. does not accept liability for any error or omission, or for any reliance placed on the information contained in this document.
  • Page 3 ● Measure, control and verify environmental performance through internal and external audits. ● Continually improve our environmental performance. CE Directive Airedale certify that the equipment detailed in this manual conforms with the following EC Directives: Electromagnetic Compatibility Directive (EMC) 2014/30/EU...
  • Page 4 IMPORTANT The information contained in this manual is critical to the correct operation and maintenance of the unit and should be read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit. Safety The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/ electrical equipment, care must be taken if you are to obtain the best results.
  • Page 5: Table Of Contents

    Precision Air Conditioning SmartCool™ 6 - 200kW Contents Introduction Construction SN, SR Units SD Units System Configurations SN, SR Nomenclature SD Nomenclature Unit Overview SN, SR Range SD Range Chilled Water Components Airflow Components Electrical Components Electric Heating Humidification Controls General Features Installation Data Dimensions...
  • Page 6 SmartCool™ 6 - 200kW Precision Air Conditioning Contents Technical Data SD CH00 Units Mechanical and Electrical Data Waterside Pressure Drop Data Sound Data Interconnecting Wiring Technical Data SD CL00 Units Mechanical and Electrical Data Waterside Pressure Drop Data Sound Data Interconnecting Wiring Technical Data SD CHCH Units Mechanical and Electrical Data...
  • Page 7: Introduction

    Based on nominal unit capacities 24°C 45% RH 7°C /12°C Water Based on nominal unit capacities 35°C 24% RH 18°C / 24°C Water ASHRAE Allowable Operating Envelope ASHRAE Recommended Operating Envelope Airedale Extended Operating Envelope 1 + 2 Airedale Operating Envelope Moisture Content Operating Band Dry Bulb Temperature (°C)
  • Page 8: Construction

    SmartCool™ 6 - 200kW Precision Air Conditioning Precision Air Conditioning System The computer room air conditioning equipment shall be designed specifically for precision temperature and humidity control applications. It shall automatically monitor and control cooling, heating, humidification, de-humidification and filtering functions for the conditioned space. The system shall be built to the highest quality engineering and manufacturing standards and shall be subject to a functional test prior to leaving the factory.
  • Page 9: System Configurations

    Precision Air Conditioning SmartCool™ 6 - 200kW System Configurations SN, SR Range SD Range SN C000 Units SD CL00 / CLCL Units ● Fans located within unit ● Fans located within floorstand ● Separate floorstand (min 350mm) ● Floorstand integral to unit (min 600mm) SR C000 / C0C0 Units SD CH00 / CHCH Units ●...
  • Page 10 SmartCool™ 6 - 200kW Precision Air Conditioning Single Circuit System Configuration (SN C000, SR C000, CL00, CH00) Dual Circuit System Configuration (SR C0C0, SD CLCL, SD CHCH) SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 11: Sn, Sr Nomenclature

    Precision Air Conditioning SmartCool™ 6 - 200kW SN, SR Nomenclature C000 Product Name SmartCool Regular Case (890mm deep) Variant Narrow Case (600mm deep) 684 mm 963 mm Case Width 1242 mm 1521 mm 1800 mm Flow Configuration Downflow Nominal Cooling Capacity (kW) Separator C000 Single Circuit CW...
  • Page 12: Unit Overview

    SmartCool™ 6 - 200kW Precision Air Conditioning Unit Overview SN, SR Range Cooling Coil Hinged Control Panel Electric Heat Humidification Chilled Water Valves Fans SD Range Air Filters Humidifier Fixed Control Panel Chilled Water Pipework Floor Height Floorstand SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 13 Precision Air Conditioning SmartCool™ 6 - 200kW Chilled Water Components SN, SR Range Cooling Coil Chilled Water Valves SD Range Cooling Coil Valves Pipework Connections SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 14: Chilled Water Components

    SmartCool™ 6 - 200kW Precision Air Conditioning Chilled Water Components System Configuration Range Single Single Dual Single Dual Number of Circuits ● ● ● ● ● Hydrophilic Epoxy Coated RTPF Chilled Water Coil ● ● ● ● ● 0-10 Volts Chilled Water Regulating Valve (2 Way) ○...
  • Page 15 Precision Air Conditioning SmartCool™ 6 - 200kW Water Connection Types SN06 SN09 SN12 SR09 SR12 SR15 SR18 SD18 SD22 SD25 SD31 SD35 ● ● ● ● ● ● ● ● ● ● ● ● Sweat Copper Connection ○ ○ ○ ○...
  • Page 16 SmartCool™ 6 - 200kW Precision Air Conditioning Chilled Water Valves Chilled Water Valve Options SN06 SN09 SN12 SR09 SR12 SR15 SR18 SD18 SD22 SD25 SD31 SD35 ● ● ● ● ● ● ● ● ● ● ● ● 2 Port Chilled Water Valves 2 Port Chilled Water –...
  • Page 17 Precision Air Conditioning SmartCool™ 6 - 200kW 0-10 Volts DC 2 Port Chilled Water Regulating Valve (SN, SR, SD Units) For systems with variable speed pumps and water flow, a 2 port control valve can be fitted. The two port valve has a shut off pressure of 13.6 Barg.
  • Page 18 SmartCool™ 6 - 200kW Precision Air Conditioning Pressure Independant Control Valve (PICV) Pressure Independant Control Vales (PICV) fitted to the SmartCool ensure that constant waterflow is achieved. The PICV valves maintain the design flowrate based upon the valve setup. SN / SR Units Valve DN20 DN25...
  • Page 19: Airflow Components

    Precision Air Conditioning SmartCool™ 6 - 200kW Airflow Components System Configuration Range Number of Circuits Single Single Dual Single Dual ● ● ● – – EC Backward Curved Centrifugal Fans in Unit – – – ● ● EC Backward Curved Centrifugal Fans in Floorstand ●...
  • Page 20 SmartCool™ 6 - 200kW Precision Air Conditioning Electronically Commutated (EC) Fan Motor EC motors incorporate integrated electronics to convert AC power to DC for efficient and accurate speed control and are adjustable via the microprocessor display keypad. The fans offer maximum air flow performance while keeping sound levels to a minimum. It gives the flexibility of connecting to AC mains with the efficiency and simple speed control of a DC motor.
  • Page 21: Electrical Components

    Precision Air Conditioning SmartCool™ 6 - 200kW Electrical Components System Configuration Range Number of Circuits Single Single Dual Single Dual ● ● ● ● ● Door Interlocked Mains Isolator ● ● ● ● ● Electrical Switch Gear ● ● ● ●...
  • Page 22 SmartCool™ 6 - 200kW Precision Air Conditioning Electrical Panels The control panel contains the necessary contactors, transformer, sub circuit protection, volt free contacts for a common alarm and mains and inter-connecting terminals. The panel is situated within the cabinet and is hinged to allow for essential maintenance of other components within the unit (SN, SR Units only).
  • Page 23: Electric Heating

    Precision Air Conditioning SmartCool™ 6 - 200kW Electric Heating SN, SR Units These shall be multi-stage finned electric heating elements complete with auto and manual reset overheat cut-out protection, element shall be phase balanced for increased efficiency. The electric heating elements are designed to be located between coil blocks, prior to fans. This enables the unit to effectively re-heat the air and evenly distribute the temperature within the floor void.
  • Page 24: Humidification

    SmartCool™ 6 - 200kW Precision Air Conditioning Humidification SN and SR Ranges The SmartCool SN and SR range have configurable humidification selections delivering 3, 8,15 kg/hr: ● SN06 configurable with 3kg/hr only ● SN09 - SR15 configurable between 3 - 8kg/hr ●...
  • Page 25 Optimised Lifetime The life span of the Airedale humidification system shall be optimised by the inclusion of a water conductivity sensor into the bottle feed. This sensor shall determine the conductivity level of the supply water and by using an algorithm embedded in the software, determines the frequency that the bottle should be drained.
  • Page 26 As standard the humidifier shall be fitted with the standard conductivity cylinder which shall cover the majority of water supplies. Where the water conductivity is known, please specify at order. For further details please contact Airedale. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 27 Precision Air Conditioning SmartCool™ 6 - 200kW Dual Power Supply The SmartCool range shall be designed with dual power supply capability, so that in the event of a power failure the supply can be switched from utility to an alternative power supply (such as second utility or generator). A dual power supply changeover switch shall be provided to enable continuous power to the SmartCool in order to reduce unit downtime and therefore loss of cooling to a minimum.
  • Page 28: Controls

    SmartCool™ 6 - 200kW Precision Air Conditioning Controls Display for illustration only System Configuration Range Number of Circuits Single Single Dual Single Dual ● ● ● ● ● PCO5 Microprocessor ● ● ● ● ● Airetronix Controls ● ● ● ●...
  • Page 29 Precision Air Conditioning SmartCool™ 6 - 200kW Vu™ The units shall be supplied with a European ROHS Directive 2002/95/EC compatible microprocessor controller connected to a 4.3” colour resistive TFT LCD touch screen display. The microprocessor controller offers powerful analogue and digital control to meet a wide range of monitoring and control features including a real time clock and industry standard communication port and network connections.
  • Page 30 SmartCool™ 6 - 200kW Precision Air Conditioning PGD1 The units shall be supplied with a European ROHS Directive 2002/95/EC compatible microprocessor controller connected to an 8 x 22 back-lit LCD keypad display. LEDs shall not be acceptable. The microprocessor controller offers powerful analogue and digital control to meet a wide range of monitoring and control features including a real time clock and Industry standard communication port and network connections.
  • Page 31 The control system integrity shall be maintained by restricting access with a password PIN number. IMPORTANT To change the PIN , please contact Airedale at time of order with the preferred 4 digit number. Remote On/Off Terminals for interlocking shall be provided to enable or disable the unit remotely.
  • Page 32 Networked units shall be configured to duty rotate, providing equal hours run of fans. BMS Interface Cards BMS Interface Card controlled units shall be interfaced with most BMS, factory fitted, please contact Airedale. A wide range of protocols shall be accommodated through the use of interface devices. Available as a standard option are: ModBus / Jbus, and Carel.
  • Page 33 6mm flamtronix tubing routed back into the control panel of the unit (the tubing must not be obstructed / damaged to ensure accurate pressure control). The contant pressure system shall be commissioned by Airedale following routing of tubing from the pressure diffuser and the unit.
  • Page 34: General Features

    Straight and L shaped Ceiling Duct Extension Straight and ‘L’ shaped duct extensions up to a height of 1350mm shall be constructed and finished to match the unit. For extensions greater than 1350mm, please contact Airedale. Height shall be specified at order.
  • Page 35 Precision Air Conditioning SmartCool™ 6 - 200kW Condensate Pumps The SmartCool condensate pump shall be either hot water (full function units when a humidifier is fitted) or cold water type (cooling only). Performance The following graphs illustrate the TOTAL static (head) pressure available. The system horizontal pipe losses and vertical lift should be factored in when calculating the condensate pump performance.
  • Page 36: Installation Data

    SmartCool™ 6 - 200kW Precision Air Conditioning Installation Data Dimensions SN/SR Depth Length Length Height Depth SN06D 1980 SN09D 1980 SN12D 1242 1980 SR09D 1980 SR12D 1242 1980 SR15D 1521 1980 SR18D 1800 1980 Detail of the doors and return air ducting centres is available from the general arrangement drawings upon request. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 37 Precision Air Conditioning SmartCool™ 6 - 200kW Installation Data Dimensions Depth Length Length Height Depth SD18D 1800 1980 SD22D 2200 1980 SD25D 2500 1980 SD31D 3100 1980 SD35D 3500 1980 Detail of the doors and return air ducting centres is available from the general arrangement drawings upon request. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 38: Lifting

    ● Check the unit is as ordered. Discrepancies or transit damage should be reported to Airedale immediately. ● This small footprint unit is relatively tall and heavy. Care should be taken during handling and lifting, that the unit is well supported and properly balanced.
  • Page 39: Minimum Unit Clearance Sn, Sr

    (2) Shaded area indicates minimum service and maintenance requirements. The unit must be installed with allowance for carpet tile clearance. (3) Dimension C denotes recommended minimum/maximum floor stand height, refer to Airedale for special applications, please specify at order. (4) Min = Threaded foot at minimum extension (additional to “C” dimension).
  • Page 40: Minimum Unit Clearance Sd

    (2) Shaded area indicates minimum service and maintenance requirements. The unit must be installed with allowance for carpet tile clearance. (3) Dimension C denotes recommended minimum/maximum floor stand height, refer to Airedale for special applications, please specify at order. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 41 Precision Air Conditioning SmartCool™ 6 - 200kW Pipework Schematics SN/SR Single Circuit SN06 SN/SR09 SN/SR12 SR15 SR18 2 COILS 3 COILS 4 COILS 5 COILS 6 COILS OPTIONAL Internal Pipework OPTIONAL OPTIONAL Floor Customer Connections Ensure binder points are installed on both inlet/outlet pipes post unit.
  • Page 42 SmartCool™ 6 - 200kW Precision Air Conditioning Pipework Schematics SR Dual Circuit OPTIONAL OPTIONAL OPTIONAL SR09 SR12 SR15 SR18 3 COILS 4 COILS 5 COILS 6 COILS Internal Pipework OPTIONAL OPTIONAL Floor Customer Connections Ensure binder points are installed on both inlet/outlet pipes post unit.
  • Page 43 Precision Air Conditioning SmartCool™ 6 - 200kW Pipework Schematics SD Single Circuit CHILLED WATER COIL OPTIONAL BYPASS PDZAL OUTLET LEG INLET LEG SD Dual Circuit Dual circuit units have two single circuits duplicated. 2 WAY DIFFERENTIAL REGULATING BINDER POINT DRAIN VALVE PDZAL PRESSURE TRANDUCER BALL VALVE...
  • Page 44: Incoming Services

    SmartCool™ 6 - 200kW Precision Air Conditioning Incoming Services SN Single Circuit VIEW FROM ABOVE FRONT OF UNIT 163.8 DIA 22mm WATER INLET DIA 22mm WATER OUTLET POWER (CONNECT VIA EXTERNAL CONNECTION BOX) CONTROLS (CONNECT VIA CONNECTORS) CONDENSATE DRAIN (TEE TO HUMIDIFIER DRAIN - IF USED) HUMIDIFIER DRAIN (TEE TO CONDENSATE DRAIN) HUMIDIFIER FILL SR Single Circuit...
  • Page 45 Precision Air Conditioning SmartCool™ 6 - 200kW Incoming Services SR Dual Circuit VIEW FROM ABOVE FRONT OF UNIT 1800 DIA 42mm CIRCUIT 1 WATER INLET DIA 42mm CIRCUIT 1 WATER OUTLET DIA 42mm CIRCUIT 2 WATER INLET DIA 42mm CIRCUIT 2 WATER OUTLET POWER (CONNECT VIA EXTERNAL CONNECTION BOX) CONTROLS (CONNECT VIA CONNECTORS) CONDENSATE DRAIN (TEE TO HUMIDIFIER DRAIN - IF USED)
  • Page 46 SmartCool™ 6 - 200kW Precision Air Conditioning Incoming Services SD Single Circuit FLOOR LEVEL FLOOR LEVEL 2ND GLAND POINT FOR DUAL POWER OPTION WATER INLET POWER CABLE AND GLAND POINT WATER OUTLET H VARIES CLIENT SPECIFIED FLOOR VOID SD Dual Circuit FLOOR LEVEL FLOOR LEVEL 2ND GLAND POINT FOR...
  • Page 47: Glycol

    Precision Air Conditioning SmartCool™ 6 - 200kW Glycol Specific Heat Capacity (C ) (kj/kg K) Water/Glycol Ethylene Glycol (Volume) / Freezing Point °C Temperature °C 0% / 0°C 10% / -4°C 20% / -9°C 30% / -15°C 40% / -23°C 4.183 3.972 3.815...
  • Page 48: Water Detection Tape Installation

    If in doubt, it is recommended to clean the fl oor with a mild detergent. For further information, please refer to Airedale’s Technical Bulletin and Loose Part Instruction Manual. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 49: Plan Termination

    Precision Air Conditioning SmartCool™ 6 - 200kW pLAN Termination Customer Side RxTx - RxTx + RxTx - RxTx + Panel Side The plugged termination ensures that the connections are made simultaniously. CAUTION Failure to attached the cables this way may cause damage to the controller. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 50: Technical Data Sn C000 Units

    (4) Backward curved EC fan options quote electrical power. Values given for full function units with standard selections for heating, humidification, supply air fans. Other fans are available, please contact Airedale. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 51: Waterside Pressure Drop Data

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SN C000 Units Waterside Pressure Drop Data 0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 Flow Rate (l/s) SN06D010-C000 / SN06D015-C000 SN09D020-C000 / SN09D025-C000 SN12D030-C000 / SN12D035-C000 ● Includes coil, 2 or 3 port valve and pipework. To calculate 3 port valve pressure drop: ...
  • Page 52: Measurement Of Sound Data

    SmartCool™ 6 - 200kW Precision Air Conditioning Measurement of Sound Data All sound data quoted has been measured in the third-octave band limited values, using a Real Time Analyser calibrated sound intensity meter in accordance with BS EN ISO9614 Part 1: 2009. All Sound Power Levels quoted are calculated from measured sound intensity according to BS EN ISO9614 Part 1: 2009.
  • Page 53: Sound Data

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data Sound Data Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SN06D010-C000 Case Breakout Sound Pressure @ 3m Discharge Air Return Air SN06D015-C000 Case Breakout Sound Pressure @ 3m Discharge Air Return Air...
  • Page 54: Interconnecting Wiring

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SN C000 Units Interconnecting Wiring Neutral (Supply 1)   Pin No. Wire CONN17 L1 (Supply 1)   L2 (Supply 1)   583 or 584 L3 (Supply 1)  ...
  • Page 55: Technical Data Sr C000 Units

    (4) Backward curved EC fan options quote electrical power. (5) Values given for full function units with standard selections for heating, humidification, supply air fans. Other fans are available, please contact Airedale. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 56: Waterside Pressure Drop Data

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SR C000 Units Waterside Pressure Drop Data 0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 Flow Rate (l/s) SR09D030-C000 / SR09D040-C000 SR12D045-C000 / SR09D055-C000 SR15D065-C000 / SR15D075-C000 SR18D080-C000 / SR18D095-C000 Includes coil, 2 or 3 port valve and pipework.
  • Page 57: Sound Data

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SR C000 Units Sound Data Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SR09D030-C000 Case Breakout Sound Pressure @ 3m Discharge Air Return Air SR09D040-C000 Case Breakout Sound Pressure @ 3m...
  • Page 58: Interconnecting Wiring

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SR C000 Units Interconnecting Wiring Neutral (Supply 1)   L1 (Supply 1)   L2 (Supply 1)   L3 (Supply 1)   CONN17 Pin No. Wire Neutral (Supply 2) ...
  • Page 59: Technical Data Sr C0C0 Units

    (4) Backward curved EC fan options quote electrical power. (5) Values given for full function units with standard selections for heating, humidification, supply air fans. Other fans are available, please contact Airedale. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 60: Waterside Pressure Drop Data

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SR C0C0 Units Waterside Pressure Drop Data 90.0 80.0 70.0 60.0 50.0 40.0 30.0 20.0 10.0 0.00 1.00 2.00 3.00 4.00 5.00 6.00 Flow Rate (l/s) SR09D020-C0C0 / SR09D025-C0C0 SR12D030-C0C0 / SR12D035-C0C0 SR15D040-C0C0 / SR15D045-C0C0 SR18D050-C0C0 / SR 18D060-C0C0 Includes coil, 2 or 3 port valve and pipework.
  • Page 61: Sound Data

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SR C0C0 Units Sound Data Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SR09D020-C0C0 Case Breakout Sound Pressure @ 3m Discharge Air Return Air SR09D025-C0C0 Case Breakout Sound Pressure @ 3m...
  • Page 62: Interconnecting Wiring

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SR C0C0 Units Interconnecting Wiring Neutral (Supply 1)   L1 (Supply 1)   L2 (Supply 1)   L3 (Supply 1)   CONN17 Pin No. Wire Neutral (Supply 2) ...
  • Page 63: Technical Data Sd Ch00 Units

    (4) Backward curved EC fan options quote electrical power. (5) Values given for full function units with standard selections for heating, humidification, supply air fans. Other fans are available, please contact Airedale. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 64: Waterside Pressure Drop Data

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SD CH00 Units Waterside Pressure Drop Data 200.0 180.0 160.0 140.0 1 and 2 120.0 100.0 80.0 60.0 40.0 20.0 0.00 2.00 4.00 6.00 8.00 10.00 12.00 Flow Rate (l/s) SD18D110-CH00-0 SD22D140-CH00-0 SD25D175-CH00-0 SD18D110-CH00-0...
  • Page 65 Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SD CH00 Units Waterside Pressure Drop Data 180.0 160.0 140.0 120.0 100.0 80.0 60.0 40.0 20.0 0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 Flow Rate (l/s) SD31D215-CH00-0 SD35D225-CH00-0 SD31D215 - CH00 - 0 SD35D255 - CH00 - 0 Includes coil, port valve and pipework.
  • Page 66: Sound Data

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SD CH00 Units Sound Data Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SD18D110-CH00 Case Breakout Sound Pressure @ 3m Discharge Air SD22D140- Return Air CH00 Case Breakout Sound Pressure @ 3m...
  • Page 67: Interconnecting Wiring

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SD CH00 Units Interconnecting Wiring Neutral (Supply 1)   L1 (Supply 1)   L2 (Supply 1)   L3 (Supply 1)   Neutral (Supply 2)   L1 (Supply 2) ...
  • Page 68: Technical Data Sd Cl00 Units

    (4) Backward curved EC fan options quote electrical power. All other options quote shaft power. (5) Values given for full function units with standard selections for heating, humidification, supply air fans. Other Fans are available, please contact airedale. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 69: Waterside Pressure Drop Data

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SD CL00 Units Waterside Pressure Drop Data 300.0 280.0 260.0 240.0 220.0 200.0 180.0 1 and 3 160.0 140.0 120.0 100.0 80.0 60.0 40.0 20.0 0.00 2.00 4.00 6.00 8.00 10.00 12.00 Flow Rate (l/s) SD18D115-CL00-0...
  • Page 70 SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SD CL00 Units Waterside Pressure Drop Data 300.00 250.00 200.00 150.00 100.00 50.00 0.00 0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00 Flow Rate (l/s) SD31D235-CL00-0 SD35D270-CL00-0 SD31D235-CL00-0 SD35D270-CL00-0 Includes coil, 2 port valve and pipework. To calculate 2 port valve pressure drop: ...
  • Page 71: Sound Data

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SD CL00 Units Sound Data Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SD18D115-CL00 Case Breakout Sound Pressure @ 3m Discharge Air Return Air SD22D145-CL00 Case Breakout Sound Pressure @ 3m...
  • Page 72: Interconnecting Wiring

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SD CL00 Units Interconnecting Wiring Neutral (Supply 1)   L1 (Supply 1)   L2 (Supply 1)   L3 (Supply 1)   Neutral (Supply 2)   L1 (Supply 2) ...
  • Page 73: Technical Data Sd Chch Units

    (4) Backward curved EC fan options quote electrical power. (5) Values given for full function units with standard selections for heating, humidification, supply air fans. Other fans are available, please contact Airedale. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 74: Waterside Pressure Drop Data

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SD CHCH Units Waterside Pressure Drop Data 140.0 120.0 100.0 80.0 60.0 40.0 20.0 0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 Flow Rate (l/s) SD18D085-CHCH-0 SD22D105-CHCH-0 SD25D135-CHCH-0 SD18D085-CHCH-0 SD22D105-CHCH-0 SD25D135-CHCH-0 Includes coil, 2 port valve and pipework.
  • Page 75 Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SD CHCH Units Waterside Pressure Drop Data 120.00 100.00 4 and 5 80.00 60.00 40.00 20.00 0.00 0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 Flow Rate (l/s) SD31D165-CHCH-0 SD35D195-CHCH-0 SD31D165-CHCH-0 SD35D195-CHCH-0 Includes coil, 2 port valve and pipework.
  • Page 76: Sound Data

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SD CHCH Units Sound Data Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SD18D085-CHCH Case Breakout Sound Pressure @ 3m Discharge Air Return Air SD22D105-CHCH Case Breakout Sound Pressure @ 3m...
  • Page 77: Interconnecting Wiring

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SD CHCH Units Interconnecting Wiring Neutral (Supply 1)   L1 (Supply 1)   L2 (Supply 1)   L3 (Supply 1)   Neutral (Supply 2)   L1 (Supply 2) ...
  • Page 78: Technical Data Sd Clcl Units

    (4) Backward curved EC fan options quote electrical power. All other options quote shaft power. (5) Values given for full function units with standard selections for heating, humidification, supply air fans. Other Fans are available, please contact airedale. SmartCool 6 - 200kW Chilled Water Technical Manual 7674716 V1.10.0_10_2018...
  • Page 79: Waterside Pressure Drop Data

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SD CLCL Units Waterside Pressure Drop Data 250.00 200.00 150.00 100.00 50.00 0.00 0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 Flow Rate (l/s) SD18D090-CLCL-0 SD22D120-CLCL-0 SD25D140-CLCL-0 SD18D090-CLCL-0 SD22D120-CLCL-0 SD25D140-CLCL-0 Includes coil, 2 port valve and pipework.
  • Page 80 SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SD CLCL Units Waterside Pressure Drop Data 250.00 200.00 150.00 100.00 50.00 0.00 0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 Flow Rate (l/s) SD31D190-CLCL-0 SD35D225-CLCL-0 SD31D190-CLCL-0 SD35D225-CLCL-0 Includes coil, 2 port valve and pipework. To calculate 3 port valve pressure drop: ...
  • Page 81: Sound Data

    Precision Air Conditioning SmartCool™ 6 - 200kW Technical Data SD CLCL Units Sound Data Frequency (Hz) dB Overall Sound Measurement dB(A) 1000 2000 4000 8000 Discharge Air Return Air SD18D090-CLCL Case Breakout Sound Pressure @ 3m Discharge Air Return Air SD22D120-CLCL Case Breakout Sound Pressure @ 3m...
  • Page 82: Interconnecting Wiring

    SmartCool™ 6 - 200kW Precision Air Conditioning Technical Data SD CLCL Units Interconnecting Wiring Neutral (Supply 1)   L1 (Supply 1)   L2 (Supply 1)   L3 (Supply 1)   Neutral (Supply 2)   L1 (Supply 2) ...
  • Page 83: After Sales

    All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by an Airedale engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or 18 months from the date of despatch, whichever is the sooner.
  • Page 84 Head Offi ce Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY Tel: +44 (0) 113 2391000 Fax:+44 (0) 113 2507219 E-mail enquiries@airedale.com Web www.airedale.com TM_SMARTCOOL_6_200kW_7674716_1.10.0_10_2018...

Table of Contents