Performance Data - Tandem Compressor (X2) - AIREDALE LogiCool InRak Technical Manual

Hide thumbs Also See for LogiCool InRak:
Table of Contents

Advertisement

LogiCool InRak™
Technical - Direct Expansion

Performance Data - Tandem Compressor (X2)

Full Load (X2)
Unit
Air On DB / RH
25°C / 42%
30°C / 32%
35°C / 24%
40°C / 18%
25°C / 42%
30°C / 32%
35°C / 24%
40°C / 18%
Note: The shaded area indicate that the Compressor speed is modulated to achieve dew point control.
All the performance data is based on a SHR of 1.0.
Maximum duty data is based on achievable duty at maximum air volume
Performance data is based upon a unit with no filtration.
24
InRak™ Technical Manual 7462807 V1.11.0_04_2016
Gross Total Cooling (kW)
Power Input (kW)
EER
Gross Total Cooling (kW)
Power Input (kW)
EER
Gross Total Cooling (kW)
Power Input (kW)
EER
Gross Total Cooling (kW)
Power Input (kW)
EER
Gross Total Cooling (kW)
Power Input (kW)
EER
Gross Total Cooling (kW)
Power Input (kW)
EER
Gross Total Cooling (kW)
Power Input (kW)
EER
Gross Total Cooling (kW)
Power Input (kW)
EER
Ambient (°C)
25
30
35
27.62
27.62
26.66
7.29
7.29
7.97
3.79
3.79
3.34
38.23
39.06
37.62
9.49
11.34
12.54
4.03
3.44
3.00
47.69
46.39
46.76
12.16
13.33
17.07
3.92
3.48
2.74
54.42
52.89
51.26
14.11
15.69
17.37
3.85
3.37
2.95
32.02
32.02
31.01
9.18
9.18
9.89
3.49
3.49
3.14
45.98
45.41
45.95
12.97
13.46
16.98
3.55
3.37
2.71
53.52
52.45
50.75
14.55
15.58
17.20
3.68
3.37
2.95
58.46
55.55
52.13
14.18
15.15
16.45
4.13
3.67
3.17
IT Cooling
40
46
25.51
26.53
8.81
11.51
2.89
2.30
39.29
38.88
16.01
20.70
2.45
1.88
45.02
42.82
18.81
20.97
2.39
2.04
47.68
43.65
18.77
20.61
2.54
2.12
29.69
31.65
10.83
15.63
2.74
2.02
44.19
41.92
18.67
20.81
2.37
2.01
48.48
43.71
18.61
20.08
2.61
2.18
48.54
44.52
17.83
15.57
2.72
2.86