Daikin RY35GXV1 Service Manual page 62

Hide thumbs Also See for RY35GXV1:
Table of Contents

Advertisement

SiBE01-829
Troubleshooting
Check No.06
Refer to P.55
Check No.07
Refer to P.56
Check No.09
Refer to P.57
Service Diagnosis
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the stop valve.
Is it opened?
YES
Check the installation space.
Check No. 07
Check the installation
condition.
Normal
Check No. 09
Check the outdoor fan.
Normal
Check the connector connection.
Is it normal?
YES
Check No. 06
Check the heat exchanger
thermistor.
Judgment
Normal
NO
Abnormal
Abnormal
NO
Abnormal
Troubleshooting
Open the stop valve.
Change the air outlet grille
position.
Change the installation
location.
Clean the heat exchanger.
Replace the fan motor.
Repair the connector or fan
motor lead wires.
Correct the connection.
Replace the heat exchanger
thermistor.
Replace PCB.
(R8506)
51