Daikin RY35GXV1 Service Manual page 60

Hide thumbs Also See for RY35GXV1:
Table of Contents

Advertisement

SiBE01-829
4.5.2
Room Temperature Thermistor
C9
Remote
Controller
Display
Method of
The temperatures detected by the room temperature thermistor is used to determine thermistor
error.
Malfunction
Detection
Malfunction
When the room temperature thermistor input is more than 5 V, or 0 V during compressor
operation ∗ .
Decision
Conditions
Room temperature thermistor: 30 Ω or less, or 490k Ω or more.
Supposed
Causes
Troubleshooting
Check No.06
Refer to P.55
Service Diagnosis
(Reference)
Faulty thermistor
Faulty PCB
Be sure to turn off power switch before check the resistance value, or
Caution
parts damage may be occurred.
Check No. 06
Check the thermistor resistance
value.
Is it normal?
YES
NO
Troubleshooting
Replace the thermistor.
(Replace the display PCB.)
Replace the indoor unit PCB.
(R8505)
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents