SiBE01-829
Step
3
Remove the putty.
Heat up the brazed part
4
of the suction side and
disconnect.
5
Lift the compressor up
and remove it.
Removal Procedure
Procedure
Points
Cautions for restoration
1. Restore the piping by non-
oxidation brazing.
2. It is required to prevent the
carbonization of the oil inside
the four way valve and the
deterioration of the gaskets
affected by heat. For the
sake of this, wrap the four
way valve with wet cloth and
provide water so that the
cloth will not be dried and
avoid excessive heating.
(Keep below 120°C)
Note: Do not use a metal
(R8561)
saw for cutting pipes by all
means because the sawdust
come into the circuit.
(R8562)
(R8563)
Outdoor Unit
99