Carrier 50TFF007-014 Product Data page 27

Single-package rooftop units electric cooling with electric heat option 50 hz
Table of Contents

Advertisement

FAN PERFORMANCE (ENGLISH) — VERTICAL DISCHARGE UNITS (cont)
50TFF012 (8.3 TONS) — STANDARD MOTOR (BELT DRIVE)
Airflow
0.2
0.4
(Cfm)
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
2500
471
369
552
2600
483
404
562
2700
495
449
573
2800
508
485
583
2900
521
530
594
3000
532
630
605
3100
544
677
616
3200
557
716
628
3300
570
763
639
3400
583
818
651
3500
596
867
663
3600
609
924
674
3700
622
989
686
3800
635
1047
698
3900
649
1123
713
4000
662
1190
722
4100
675
1267
734
4200
689
1353
746
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 690 to 900 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. See
50TFF014 (10.2 TONS) — STANDARD MOTOR (BELT DRIVE)
Airflow
0.2
0.4
(Cfm)
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
3100
570
623
636
3200
584
676
649
3300
598
728
662
3400
612
781
675
3500
626
873
688
3600
640
913
702
3700
654
1065
714
3800
668
1129
727
3900
683
1194
741
4000
697
1267
754
4100
711
1340
767
4200
726
1423
780
4300
741
1506
794
4400
755
1598
808
4500
770
1700
821
4600
784
1794
835
4700
799
1905
849
4800
814
2009
863
4900
829
2131
877
5000
843
2246
892
5100
858
2378
906
LEGEND
Bhp
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 710 to 890 rpm. Other rpms may require a
field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that the full
range of the motor can be utilized with confidence. Using your fan motors
up to the wattage ratings shown will not result in nuisance tripping or
0.6
0.8
494
617
611
679
719
530
627
656
685
773
575
638
710
694
827
620
648
755
704
881
665
659
809
714
944
763
670
891
725
1014
803
680
940
735
1081
859
690
998
746
1148
907
700
1064
757
1216
965
711
1123
767
1284
1031
721
1190
777
1353
1097
732
1267
787
1430
1165
744
1335
797
1508
1241
755
1413
808
1595
1318
767
1491
818
1683
1396
778
1578
829
1779
1482
790
1674
839
1875
1569
801
1761
851
1971
0.6
0.8
799
693
886
748
1044
842
705
948
759
1097
904
717
1027
769
1158
957
729
1115
780
1229
1018
741
1202
792
1299
1080
754
1290
803
1378
1218
767
1373
815
1514
1291
780
1456
827
1598
1365
793
1540
839
1691
1448
806
1624
851
1785
1531
819
1708
864
1879
1624
832
1802
877
1983
1717
845
1897
889
2096
1819
858
2000
902
2210
1923
871
2114
915
2325
2027
884
2219
928
2450
2140
897
2343
941
2566
2254
910
2468
954
2692
2378
923
2602
967
2828
2503
937
2746
980
2964
2629
950
2891
993
3111
External Static Pressure (in. wg)
1.0
1.2
740
818
757
881
754
881
765
944
757
944
775
1007
759
1007
791
1070
766
1070
807
1150
778
1148
825
1275
787
1216
835
1353
796
1284
844
1430
805
1353
854
1508
815
1430
863
1587
826
1517
871
1665
836
1595
880
1753
847
1691
890
1849
857
1779
901
1945
867
1866
912
2050
878
1962
922
2203
888
2058
933
2309
898
2212
943
2424
Evaporator-Fan Motor Performance table on page 30 for additional
information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
Motor Efficiency: .83
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be added to
external static pressure before entering Fan Performance table.
External Static Pressure (in. wg)
1.0
1.2
800
1202
850
1281
809
1281
858
1352
819
1342
867
1483
829
1414
876
1589
840
1483
886
1676
851
1553
896
1755
861
1666
906
1862
873
1751
916
1948
884
1836
927
2035
895
1931
938
2123
907
2035
949
2219
919
2149
960
2316
931
2263
971
2423
943
2387
983
2548
955
2512
995
2683
968
2638
1006
2828
981
2773
1018
2964
993
2919
1030
3111
1006
3065
1043
3267
1019
3221
1055
3424
1032
3388
1068
3590
premature motor failure. Unit warranty will not be affected. See
Evaporator-Fan Motor Performance table on page 30 for additional
information.
6. Use of a field-supplied motor may affect wire sizing. Contact your Carrier
representative to verify.
7. To convert Watts to Bhp:
Watts x Motor Efficiency
Bhp =
Motor Efficiency: .85
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be added to
external static pressure before entering Fan Performance table.
1.4
1.6
765
944
811
1034
889
775
1025
825
1097
907
793
1088
848
1240
929
808
1186
887
1357
954
823
1339
918
1519
963
874
1422
926
1613
974
880
1491
933
1656
983
888
1569
934
1718
988
897
1648
940
1853
989
907
1744
947
1946
991
916
1831
956
2039
997
926
1927
966
2134
1004
934
2015
976
2238
1013
943
2160
985
2344
1023
952
2265
994
2451
1032
962
2371
1003
2560
1042
973
2496
1011
2679
1051
983
2624
1021
2810
1060
746
Maximum Continuous Watts: 2120
1.4
1.6
901
1360
950 1474
989
907
1457
960 1571 1001
914
1536
963 1668 1010
922
1606
968 1764 1018
930
1773
975 1826 1021
940
1913
983 1887 1026
950
2027
991 2202 1030
959
2123
1001 2299 1040
969
2228
1010 2405 1049
979
2334
1020 2521 1059
989
2441
1029 2638 1068
1000
2548
1039 2764 1077
1011
2647
1049 2882 1087
1022
2764
1059 3010 1097
1033
2882
1070 3138 1107
1044
3010
1081 3258 1117
1056
3147
1092 3387 1127
1067
3304
1103 3525 1138
1079
3470
1114 3674 1149
1091
3637
1126 3822 1160
1103
3804
1137 4009 1171
746
Maximum Continuous Watts: 3313
1.8
2.0
1321
946
1645
1429
959
1771
1528
975
1878
1690
987
1959
1834
999
2040
1920
1012
2134
1963
1017
2177
1980
1025
2230
2031
1032
2282
2099
1038
2318
2195
1043
2380
2291
1045
2478
2397
1051
2569
2514
1059
2688
2633
1068
2819
2763
1078
2952
2895
1087
3097
3029
1090
3276
1.8
2.0
1597
1000
1755
1703
1006
1834
1799
1018
1940
1940
1022
2045
2062
1039
2203
2212
1051
2370
2361
1064
2512
2476
1075
2638
2593
1085
2773
2710
1095
2901
2837
1105
3028
2955
1114
3166
3092
1124
3304
3230
1133
3442
3368
1143
3590
3516
1152
3748
3655
1162
3897
3804
1172
4055
3934
1182
4223
4083
1193
4382
4242
1204
4531
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF