Carrier 50TFF007-014 Product Data page 22

Single-package rooftop units electric cooling with electric heat option 50 hz
Table of Contents

Advertisement

Performance data (cont)
50TFF007 (17.6 kW) — STANDARD MOTOR (BELT DRIVE)
Airflow
25
(L/s)
R/s
kW
700
12.1
0.30
750
12.8
0.36
800
13.5
0.42
850
14.2
0.56
900
14.9
0.63
950
15.7
0.72
1000
16.4
0.81
1050
17.2
0.92
1100
18.0
1.03
1150
18.7
1.17
1200
19.4
1.23
LEGEND
BkW — Fan Input kW x Motor Efficiency
kW
— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 15.50 to 20.08 r/s. Other r/s's may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
50TFF008,009 (21.5 AND 24.3 kW) — STANDARD MOTOR (BELT DRIVE)
Airflow
50
(L/s)
R/s
kW
R/s
800
7.0
0.27
9.0
900
7.5
0.37
9.3
1000
8.1
0.47
9.7
1100
8.7
0.57
10.1
1200
9.3
0.67
10.5
1300
9.8
0.80
11.0
1400
10.4
0.94
11.5
1500
11.0
1.11
12.0
LEGEND
BkW — Fan Input kW x Motor Efficiency
kW
— Kilowatt Input to Motor
NOTES:
1. Boldface indicates field-supplied drive required (see Note 3).
2.
indicates field-supplied motor and drive required.
3. Factory-shipped drive range is 10.33 to 14.67 r/s. Other r/s's may
require a field-supplied drive.
4. Values include losses for filters, unit casing, and wet coils.
5. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
your fan motors up to the kW ratings shown will not result in
22
FAN PERFORMANCE (SI) — VERTICAL DISCHARGE UNITS
50
100
R/s
kW
R/s
kW
13.1
0.36
14.8
0.48
16.4
13.7
0.42
15.5
0.56
17.0
14.4
0.49
16.1
0.63
17.5
15.1
0.61
16.7
0.74
18.1
15.8
0.70
17.3
0.82
18.7
16.5
0.78
17.9
0.91
19.3
17.2
0.88
18.6
1.02
19.9
17.9
0.99
19.2
1.13
20.6
18.6
1.10
19.9
1.26
21.2
19.2
1.23
20.6
1.41
21.8
19.8
1.36
21.3
1.55
22.4
100
150
200
kW
R/s
kW
R/s
0.45
9.6
0.53
11.0
0.55
10.1
0.66
11.4
0.65
10.6
0.79
11.8
0.75
11.1
0.92
12.2
0.85
11.6
1.05
12.6
0.99
12.1
1.21
13.0
1.13
12.6
1.38
13.5
1.31
13.0
1.58
13.9
External Static Pressure (Pa)
150
200
R/s
kW
R/s
kW
R/s
0.61
17.8
0.75
18.7
0.68
18.4
0.84
19.5
0.77
18.9
0.93
20.1
0.85
19.4
1.00
20.6
0.95
19.9
1.10
21.1
1.06
20.5
1.21
21.7
1.18
21.1
1.34
22.2
1.30
21.7
1.48
22.8
1.44
22.3
1.63
23.4
1.58
23.0
1.78
24.0
1.72
23.6
1.92
24.6
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
External Static Pressure (Pa)
250
300
kW
R/s
kW
R/s
kW
0.70
12.0
1.86
13.1
1.03
0.84
12.3
1.02
13.4
1.19
0.98
12.7
1.18
13.7
1.37
1.12
13.1
1.34
14.0
1.55
1.26
13.5
1.50
14.3
1.73
1.43
13.9
1.67
14.7
1.93
1.63
14.3
1.87
15.1
2.13
1.85
14.7
2.11
15.5
2.36
nuisance tripping or premature motor failure. Unit warranty will not
be affected. See Evaporator-Fan Motor Performance table on
page 30 or additional information.
6. Use of a field-supplied motor may affect wire sizing. Contact your
Carrier representative to verify.
7. To convert kW to bkW:
BkW = kW x Motor Efficiency
Motor Efficiency: .81
8. Interpolation is permissible. Do not extrapolate.
9. Static pressure losses (i.e., economizer, electric heater) must be
added to external static pressure before entering Fan Performance
table.
250
300
350
kW
R/s
kW
R/s
0.85
18.7
0.83
17.8
0.98
20.1
1.05
20.0
1.09
21.1
1.22
21.5
1.15
21.7
1.31
22.9
1.26
22.2
1.42
23.3
1.37
22.8
1.55
23.8
1.50
23.3
1.69
24.3
1.64
23.8
1.83
24.9
1.79
24.4
1.98
25.4
1.97
24.9
2.14
25.9
2.12
25.5
2.29
Maximum Continuous kW: 2.12
350
400
R/s
kW
R/s
kW
R/s
13.9
1.25
15.0
1.74
15.5
14.2
1.43
15.3
1.86
15.8
14.5
1.61
15.5
1.98
16.1
14.8
1.79
15.7
2.10
16.4
15.1
1.97
15.9
2.22
16.7
15.5
2.18
16.2
2.34
16.9
15.9
2.41
16.6
2.66
17.3
16.3
2.64
17.0
2.91
Maximum Continuous kW: 2.12
400
kW
R/s
kW
0.67
16.0
0.44
1.23
19.1
0.85
1.28
21.3
1.22
1.50
23.9
1.69
1.62
24.4
1.80
1.73
24.8
1.93
1.86
25.2
2.06
2.01
25.7
2.21
2.18
26.3
2.38
2.34
450
500
kW
R/s
kW
1.96
16.6
2.45
2.10
16.8
2.55
2.24
17.0
2.65
2.38
17.2
2.75
2.52
17.4
2.85
2.69
17.6
2.97
2.92