COMBIMASTER & MICROMASTER Integrated
REFERENCE MANUAL
Parameter
Function
P152 • • • •
Yellow LED function
P201
PI closed loop mode
P202 • • • •
P gain
P203 • • • •
I gain
P205 • • • •
Sample interval (x 25
ms)
P206 • • • •
Transducer filtering
P207 • • • •
Integral capture range
(%)
P208
Transducer type
P210
Transducer reading
(%)
P211 • • • •
0% setpoint
P212 • • • •
100% setpoint
P220 • • • •
PI frequency cut-off
P331
Analogue mode
P332
Fine adjustment (%)
P700
P701 • • • •
P702
Siemens plc. 1999
©
| G85139-H1731-U300-D2
Range
[Default]
0 - 5
0 = Off
1 = On
[5]
2 = Fault mode:
3 = Running mode:
4 = Not used
5 = Default mode (see table in Operating
Information Section 5).
0 = Normal operation (closed loop control
0 - 2
disabled).
[0]
1 = Not used
2 = Closed loop control using PI input for
transducer feedback.
0.0-999.9
Proportional gain.
[1.0]
0.00 -
Integral gain.
0.01 corresponds to the longest integral response time.
99.99
[0.00]
1 - 2400
Sampling interval of feedback sensor.
[1]
0 = Filter off.
0 - 255
1-255 = Low pass filtering applied to transducer.
[0]
0 - 100
Percentage error above which integral term is reset to zero.
[100]
0 - 1
0 = An increase in motor speed causes an increase in
sensor voltage/current output.
[0]
1 = An increase in motor speed causes a decrease in
sensor voltage/current output.
Read only. Value is a percentage of full scale of the PI input.
0.0 -
(eg.: 100 = 10V / 20mA)
100.0
[-]
Value of P210 to be maintained for 0% setpoint.
0.00-
100.00
[0.00]
Value of P210 to be maintained for 100% setpoint.
0.00-
100.00
[100.00]
0 = Normal operation
0 - 1
1 = Switch off inverter at or below minimum
[0]
frequency.
0 = Internal potentiometer only
0 - 4
1 = External analogue input only
[2]
2 = Internal potentiometer + external analogue input
3 = Internal potentiometer fine, external input coarse
4 = Internal potentiometer coarse, external input fine
0 - 100
Percentage of fine tuning adjustment for P331 = 3 or 4.
[10]
Specific to PROFIBUS-DP. See PROFIBUS Handbook
for further details. (Access only possible with P099 = 1.)
Description / Notes
On = Tripped
Flashing = Warning
On = Motor running
Flashing = Inverter on but motor
stationary
35