Parameter
P051
Selection control
function, DIN 1
(terminal 5), fixed
frequency 3 or binary
fixed frequency bit 0
P052
Selection control
function, DIN 2
(terminal 6), fixed
frequency 2 or binary
fixed frequency bit 1
P053
Selection control
function, DIN 3
(terminal 7), fixed
frequency 1 or binary
fixed frequency bit 2
28
Function
Range
[Default]
0-19
[1]
0-19
[2]
0-19
[10]
COMBIMASTER & MICROMASTER Integrated
Description / Notes
Value
Function of
P051 to P053
0
Input disabled
1
ON right
2
On Left
3
Reverse
4
OFF 2
5
OFF 3
6
Fixed Frequencies
1 – 3
7
Jog Right
8
Jog left
9
Remote operation
10
Fault code reset
11
Increase frequency *
12
Decrease frequency*
13
Disable analogue input
(setpoint is 0.0 Hz)
14
Disable the ability to
change parameters
15
Enable dc brake
16
Use jog ramp times
instead of normal ramp
times
(SW Version : 3.00
onwards)
17
Binary fixed frequency
control (fixed
frequencies1-7)
18
As 6, but input high will
also request RUN
19
External trip / PTC
* Only effective when P007 = 0.
Binary Coded Fixed Frequency Mapping
(P051, P052, P053 = 17)
STOP
Run to FF1 (P041)
Run to FF2 (P042)
Run to FF3 (P043)
Run to FF4 (P044)
Run to FF5 (P046)
Run to FF6 (P047)
Run to FF7 (P048)
Siemens plc. 1999
©
REFERENCE MANUAL
Function
Function
low state
high state
-
-
Off
On Right
Off
On Left
Normal
Reverse
OFF 2
On
Off 3
On
Off
On
Off
Jog right
Off
Jog left
Local
Remote
Off
Reset on
rising edge
Off
Increase
Off
Decrease
Analogue
Analogue
on
disabled
'P' Enabled 'P' disabled
Off
Brake on
Normal
Jog Ramp
Times
Off
On
Off
On
Trip (F012) No Trip
DIN3
DIN2
DIN1
(P053)
(P052)
(P051)
0
0
0
0
0
1
0
1
0
0
1
1
1
0
0
1
0
1
1
1
0
1
1
1