Field Setting
(13) Setting of Normal Air Flow
Make the following setting according to the ceiling height. The setting position No. is set to "01"
at the factory.
13 (23)
13 (23)
13 (23)
13 (23)
*1 "Mode No." setting is done in a batch for the group. To make or confirm settings for an
*2 The figure of the ceiling height is for the all round outlet. For the settings for four-direction
96
In the Case of FXAQ
Setting Switch
Mode No.
No.
13(23)
0
In the Case of FXHQ
Mode No.
First code No.
13(23)
0
In the Case of FXFQ20~80 (All round outlet)
First
Second
Mode
code
code
No.
No.
No.
Standard • All
01
round outlet
0
02
High Ceiling (1)
03
Higher Ceiling (2)
In the Case of FXFQ100~125 (All round outlet)
First
Second
Mode
code
code
No.
No.
No.
Standard • All
01
round outlet
0
02
High Ceiling (1)
03
Higher Ceiling (2)
In the Case of FXFQ20~80 (*
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 4.0 m Lower than 3.5 m
In the Case of FXFQ100~125 (*
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 4.5 m Lower than 4.2 m
individual unit, set the internal mode number in parentheses.
(part of corner closed off), three-direction and two-direction outlets, see the installation
manual and technical guide supplied with the separately sold closure material kit.
Setting Position
No.
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
Second code
No.
01
02
Setting
Setting
2
4-Way, 3-Way, 2-Way Outlets)
Setting
4-way Outlets
Lower than 3.1 m Lower than 3.0 m Lower than 3.5 m
Lower than 3.4 m Lower than 3.3 m Lower than 3.8 m
2
4-Way, 3-Way, 2-Way Outlets)
Setting
4-way Outlets
Lower than 3.4 m Lower than 3.6 m Lower than 4.2 m
Lower than 3.9 m Lower than 4.0 m Lower than 4.2 m
SiBE34-802
Setting
Ceiling height (m)
2.7 or less
2.7-3.5
Ceiling height (m)
≤2.7
2.7-3
3-3.5
Ceiling height (m)
≤3.2
3.2-3.6
3.6-4.2
Ceiling height
3-way Outlets
2-way Outlets
Ceiling height
3-way Outlets
2-way Outlets
Test Operation