Field Setting
(18) External Static Pressure Settings (for FXMQ-P model)
The "SECOND CODE NO." is set to 07 (an external static pressure of 100 Pa) at factory set.
*1 The FXMQ50 · 63 · 80 · 100 · 125PVE cannot be set to 30 Pa.
*2 The FXMQ40PVE cannot be set to 180 or 200 Pa.
(19) Humidification When Heating Thermostat is OFF
Setting to "Humidification Setting" turns ON the humidifier if suction temperature is 20ºC or
above and turns OFF the humidifier if suction temperature is 18ºC or below when the heating
thermostat is OFF.
(20) Setting of Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected. The indoor fan carries
out residual operation for one minute after the thermostat is stopped. (For the purpose of
preventing dust on the air filter from falling off.)
(21) Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the
unit, this setting is unnecessary.
98
MODE NO.
FIRST CODE NO.
13 (23)
Mode No.
First Code No.
15 (25)
Mode No.
First Code No.
15 (25)
Mode No.
First Code No.
15 (25)
SECOND CODE NO.
01
02
03
04
05
06
07
06
08
09
10
11
12
13
14
15
Second Code No.
01
1
02
Second Code No.
01
2
02
Second Code No.
01
3
02
SiBE34-802
External Static Pressure
30Pa (*1)
50Pa
60Pa
70Pa
80Pa
90Pa
100Pa
110Pa
120Pa
130Pa
140Pa
150Pa
160Pa
180Pa (*2)
200Pa (*2)
Setting
Setting of humidifier
Contents
Without direct duct
connection
With direct duct
connection equipped
with fan
Contents
Individual operation of
humidifier
Interlocked operation
between humidifier and
drain pump
Test Operation