Air Tight Test And Vacuum Drying; Additional Refrigerant Charge - Daikin RXYSQ4-5-6PA7V1B Service Manual

Vrv iii-s
Table of Contents

Advertisement

SiBE34-802

1.1.3 Air Tight Test and Vacuum Drying

After evacuating the system for 2 hours, pressurize the system to 0.05 MPa (vacuum break)
with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to –100.7
kPa (vacuum drying). If the system cannot be evacuated to –100.7 kPa within 2 hours, repeat
the operation of vacuum break and vacuum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that the vacuum gauge does not
rise.

1.1.4 Additional Refrigerant Charge

Test Operation
Air tight test: Make sure to use nitrogen gas.
Pressurize the liquid and gas pipes to 4.0 MPa (40 bar) (do not pressurize more than 4.0
MPa (40 bar)). If the pressure does not drop within 24 hours, the system passes the test. If
the pressure drops, check where the nitrogen leaks from.
Vacuum drying: Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr, –755 mm
Hg)
1. Evacuate the system from the liquid and gas pipes by using a vacuum pump for more
than 2 hours and bring the system to –100.7 kPa. After keeping the system under that
condition for more than 1 hour, check if the vacuum gauge rises or not. If it rises, the
system may either contain moisture inside or have leaks.
2. Following should be executed if there is a possibility of moisture remaining inside the
pipe (if piping work is carried out during the raining season or over a long period of time,
rainwater may enter the pipe during work).
Refrigerant cannot be charged until field wiring has been completed.
Refrigerant may only be charged after performing the leak test and the vacuum drying (see
above).
When charging a system, care shall be taken that its maximum permissible charge is never
exceeded, in view of the danger of liquid hammer.
Charging with an unsuitable substance may cause explosions and accidents, so always
ensure that the appropriate refrigerant (R-410A) is charged.
Refrigerant containers shall be opened slowly.
Always use protective gloves and protect your eyes when charging refrigerant.
When performing service on the unit requiring the refrigerant system to be opened,
refrigerant must be evacuated according to local regulations.
Do not use the automatic refrigerant charging function while working on the indoor units.
When using the automatic refrigerant charging function, the indoor units operate
automatically as well as the outdoor unit.
When the power is on, please close the front panel when leaving the unit.
Pressure reducing valve
Tank
Nitrogen
Measuring
instrument
Outdoor unit
Gas line stop valve
Liquid line stop valve
Stop valve service port
Valve A
Vacuum
Charge hose
pomp
Fig. 6
Test Operation
Indoor unit
Indoor unit
75

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxysq4-5-6pa7y1b

Table of Contents