Method of Replacing the Inverter's Power Transistors Modules
Power module checking
When using the digital type of multiple tester, make measurement in diode check mode.
Tester terminal
+
C+
U
V
W
U
V
W
C-
The following abnormalities are also doubted besides the PC board abnormality.
1 Faulty compressor (ground fault, ground leakage)
1 Faulty fan motor (ground leakage)
256
Criterion
-
U
Not less than 0.3V
(including ∞)*
V
W
C-
Not less than 0.3V
(including ∞)*
C+
0.3 to 0.7V
(including ∞)*
U
0.3 to 0.7V
(including ∞)*
V
W
*There needs to be none of each value variation.
SiBE34-802
Remark
It may take time to
determine the voltage
due to capacitor
charge or else.
Appendix