Environmental Type Tests - Siemens RUGGEDCOM RS930L Installation Manual

Hide thumbs Also See for RUGGEDCOM RS930L:
Table of Contents

Advertisement

RUGGEDCOM RS930L
Installation Guide
Test
IEC 60255-5
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RS930L meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
IEEE Test
C37.90.3
C37.90.2
C37.90.1
C37.90

Environmental Type Tests

Test
IEC 60068-2-1
IEC 60068-2-2
EMI and Environmental Type Tests
Description
Dielectric Strength
HV Impulse
IEEE 1613
Clause
9
ESD
8
Radiated RFI
7
Fast Transient
Oscillatory
6
HV Impulse
Dielectric
Strength
Description
Cold Temperature
Dry Heat
Signal ports
2 kVAC (Fail-Safe Relay output)
DC Power ports
AC Power ports
Signal ports
5 kV (Fail-Safe Relay Output)
DC Power ports
AC Power ports
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Test Ad
-40 °C (-40 °F), 16 Hours
Test Bd
85 °C (185 °F), 16 Hours
Test Levels
1.5 kVDC
2 kVDC
5 kV
5 kV
Test Levels
+/- 8 kV
+/- 15 kV
35 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
2.5 kV common mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kVAC (Failsafe Relay)
1.5 kVDC
2 kVAC
Test Levels
Severity Levels
Chapter 6
Certification
Severity Levels
23

Advertisement

Table of Contents
loading

Table of Contents