2.1

General specifications

For items not listed below, specifications are the same as the of the PLC main unit.
For general specifications, refer to the manual of the PLC main unit.
Item
Dielectric withstand voltage
Insulation resistance
2.2

Power supply specification

External power
supply
2.3

Performance specification

Item
CC-Link applicable version
Station type
Station number
Transmission rate
Transmission distance
Number of occupied stations
Setting items
Communication method
Synchronous method
Encoding method
Transmission path type
Transmission format
Error control method
Connection cable
Number of I/O occupied points
Number of connectable units to the
main unit
*1.
When the setting of the 64CCL is the single setting, please set up the master station as a
Ver.1 intelligent device station. When the setting of the 64CCL are the double setting, the quadruple
setting, or the octuple setting, please set up the master station as a Ver.2 intelligent device station.
500V AC for one minute
5M
or more by 500V DC Megger
Item
Power supply voltage
24V DC +20% -15% Ripple (p-p) within 5%
Permitted instantaneous
Operation continues when the instantaneous power failure is shorter than PS1:1ms.
power failure time
Current consumption
220mA
Ver.2.00 (Ver.1.10 also supported.)
Intelligent device station
1 to 64
156Kbps/625Kbps/2.5Mbps/5Mbps/10Mbps
In accordance with the CC-Link specification. Refer to the PLC main unit manual for details.
1 to 4 stations
Station number, Transmission rate, Number of occupied stations, Expanded cyclic setting
Broadcast polling system
Flag synchronization method
NRZI method
Bus (RS-485)
Conforms to HDLC
16
12
5
CRC(X
+X
+X
CC-Link dedicated cable/ CC-Link dedicated high-performance cable/
Ver.1.10 compatible CC-Link dedicated cable
8 points
1
→ Refer to FX
Specification
Conforming to JEM-1021
Between all terminals and ground terminal
Specification
Specification
*1
+1)
2 Specification and function
2.1 General specifications
→ Refer to FX
Hardware Edition
3G
→ Refer to FX
Hardware Edition
3U
Hardware Edition
3UC
1
2
3
4
5
6
7
8
9
A
15

Advertisement

Table of Contents
loading

Table of Contents