REFRIGERANT PIPE CONNECTION

Drain joint installation
NOTE: The drain joint differ from appliance to
appliance.
Fit the seal into the drain joint, then insert the drain joint into
the base pan hole of outdoor unit, rotate 90° to securely
assemble them. Connecting the drain joint with an extension
drain hose (Locally purchased), in case of the water draining
off the outdoor unit during the heating mode.
Refrigerant pipe connection
1. Flaring work
Main cause for refrigerant leakage is due to
defect in the flaring work. Carry out correct
flaring work using the following procedure:
A: Cut the pipes and the cable.
1. Use the piping kit accessory or pipes
purchased locally.
2. Measure the distance between the indoor and the outdoor
unit.
3. Cut the pipes a little longer than the measured
distance.
4. Cut the cable 1.5m longer than the pipe length.
B: Burr removal
1. Completely remove all burrs from the cut cross section of
pipe/tube.
2. Put the end of the copper tube/pipe in a downward
direction as you remove burrs in order to avoid dropping
burrs into the tubing.
C: Putting nut on
Remove flare nuts attached to indoor and outdoor unit,
then put them on pipe/tube
having completed burr removal.(not possible
to put them on after flaring work)
D: Flaring work
Firmly hold copper pipe in a die in the dimension shown in
the table below.
Outer diam. (mm)
6.35
Φ
9.52
Φ
12.7
Φ
A(mm)
Max.
Min.
1.3
0.7
1.6
1.0
1.8
1.0
Flare nut
Copper tube
10
Fig.57