Main Safety Isolating Transformer - Vaillant ECOmax VUW 236 EH Instructions For Installation And Servicing

Table of Contents

Advertisement

Disconnect the flue from the top of
boiler as described in Section 4.7.
Remove boiler from wall and
slacken two screws (1, fig. 76).
Slide expansion vessel upwards
and out of boiler casing.
Reassemble in reverse order.
Re-mount the boiler (see Section
4.6).
Re-commission the boiler
(see Section 5).
OR
A suitable replacement expansion ves-
sel can be fitted externally to the boi-
ler as described in Section 3.7.5 (if
possible on the central heating return
in an accessible position). In these cir-
cumstances, the replacement expansi-
on vessel must be correctly sized igno-
ring the original expansion vessel
which can be left in position on the
boiler.
7.12 Replacement of main
safety isolating
transformer
Isolate boiler from the electricity
supply.
Remove front casing as in Section
7.1.3
Lower front control panel as in
Section 7.1.6.
Remove condensate trap as in
Section 7.7.
Remove back of control box by
undoing the 2 screws (1, fig. 78).
Unplug transformer plugs (1, fig.
79) and remove from control box.
fig. 78
fig. 79
47