5.0 Power Measurement Procedures

5.1
1Φ2W (Single Phase - Two Wire) Measurement
1.
Power the instrument ON by pressing the 'Power' key (item 3-7; Section 3 diagrams), and
then use the '1Φ 3Φ' key (item 3-22) to select the 1Φ 2W system, the selected name of the
system will be shown on the bottom left side of the display (refer to Figure 5-1 below)
2.
Connect the line voltage L1, Vn (Neutral) to V1 and N terminals of the
instrument.
3.
Connect the Clamp (A1) to the conductor (A1)
4.
Connect Clamp 1 (A1) to the A1 terminal of the instrument
5.
The related measurement factors will appear on the display
6.
Measurement definitions can be found in Section 5-15
Figure 5-1
21
PQ3470-en-GB_V1.9 10/15