Power Supply - Carrier AquaSnap 30RAP010-150 Installation Instructions Manual

Liquid chillers with puron refrigerant r-410a
Table of Contents

Advertisement

Table 17 — 30RAP Electrical Data — Dual Point, Hydronic Package with
38RAP UNIT
VOLTAGE
SIZE
V-Hz (3 Ph)
208/230-3-60
380-3-60
070
460-3-60
575-3-60
208/230-3-60
380-3-60
080
460-3-60
575-3-60
208/230-3-60
380-3-60
090
460-3-60
575-3-60
208/230-3-60
380-3-60
100
460-3-60
575-3-60
208/230-3-60
380-3-60
115
460-3-60
575-3-60
208/230-3-60
380-3-60
130
460-3-60
575-3-60
208/230-3-60
380-3-60
150
460-3-60
575-3-60
38RAP UNIT
VOLTAGE
SIZE
V-Hz (3 Ph)
208/230-3-60
380-3-60
070
460-3-60
575-3-60
208/230-3-60
380-3-60
080
460-3-60
575-3-60
208/230-3-60
380-3-60
090
460-3-60
575-3-60
208/230-3-60
380-3-60
100
460-3-60
575-3-60
208/230-3-60
380-3-60
115
460-3-60
575-3-60
208/230-3-60
380-3-60
130
460-3-60
575-3-60
208/230-3-60
380-3-60
150
460-3-60
575-3-60
LEGEND
ICF
— Instantaneous Current Flow
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit ter-
minals is not below or above the listed minimum and maximum limits. Maximum allow-
able phase imbalance is: voltage, 2%; amps 10%.
2. All units/modules have dual point primary power connection. (Each unit/module
requires its own power supply.) Main power must be supplied from a field-supplied
disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect and heater safety device are on.
4. Power draw control circuits include cooler heaters (where used).
Standard Low-Sound AeroAcoustic™ Fan (cont)
PUMP SIZE 10.0 hp
CIRCUIT 1
MCA
MOCP
ICF
155.6
200
425.8
96.0
125
249.5
75.0
100
220.4
65.3
80
167.7
202.7
250
438.6
110.8
125
216.2
92.5
110
213.6
79.1
90
163.2
217.4
250
487.6
133.9
150
287.4
104.8
125
250.2
91.4
110
193.8
234.8
300
677.0
127.3
175
380.7
105.0
125
313.0
85.4
110
253.0
291.8
350
683.0
156.0
175
368.0
129.5
150
303.6
104.4
125
246.6
297.8
350
689.0
159.9
175
371.9
132.4
150
306.5
106.8
125
249.0
366.2
450
808.4
199.2
225
452.6
164.2
200
372.2
134.2
150
301.8
PUMP SIZE 15.0 hp
CIRCUIT 1
MCA
MOCP
ICF
202.7
250
438.6
110.8
125
216.2
92.5
110
213.6
79.1
90
163.2
217.4
250
487.6
133.9
150
287.4
104.8
125
250.2
91.4
110
193.8
234.8
300
677.0
127.3
175
380.7
105.0
125
313.0
85.4
110
253.0
291.8
350
683.0
156.0
175
368.0
129.5
150
303.6
104.4
125
246.6
297.8
350
689.0
159.9
175
371.9
132.4
150
306.5
106.8
125
249.0
366.2
450
808.4
199.2
225
452.6
164.2
200
372.2
134.2
150
301.8
REC FUSE
MCA
175
206.4
110
124.5
90
98.9
80
86.2
225
206.4
125
124.5
100
98.9
90
86.2
250
206.4
150
124.5
125
98.9
100
86.2
300
268.8
150
138.8
125
117.8
100
94.4
350
268.8
175
138.8
150
117.8
125
94.4
350
331.2
175
174.2
150
146.7
125
119.4
400
331.2
225
174.2
175
146.7
150
119.4
REC FUSE
MCA
225
218.1
125
131.5
100
104.4
90
91.0
250
218.1
150
131.5
125
104.4
100
91.0
300
280.5
150
145.8
125
123.3
100
99.2
350
280.5
175
145.8
150
123.3
125
99.2
350
342.9
175
181.2
150
152.2
125
124.2
400
342.9
225
181.2
175
152.2
150
124.2
43
PUMP SIZE 10.0 hp
CIRCUIT 2
MOCP
ICF
REC FUSE
250
476.6
225
150
278.0
150
125
244.3
110
100
188.6
100
250
476.6
225
150
278.0
150
125
244.3
110
100
188.6
100
250
476.6
225
150
278.0
150
125
244.3
110
100
188.6
100
300
660.0
300
175
350.8
150
150
291.9
150
110
236.6
110
300
660.0
300
175
350.8
150
150
291.9
150
110
236.6
110
400
773.4
400
225
427.6
200
175
354.7
150
150
287.0
150
400
773.4
400
225
427.6
200
175
354.7
150
150
287.0
150
PUMP SIZE 15.0 hp
CIRCUIT 2
MOCP
ICF
REC FUSE
250
488.3
250
150
285.0
150
125
249.8
125
110
193.4
100
250
488.3
250
150
285.0
150
125
249.8
125
110
193.4
100
350
671.7
300
175
357.8
175
150
297.4
150
125
241.4
110
350
671.7
300
175
357.8
175
150
297.4
150
125
241.4
110
400
785.1
400
225
434.6
200
175
360.2
175
150
291.8
150
400
785.1
400
225
434.6
200
175
360.2
175
150
291.8
150