Power Supply - Carrier AquaSnap 30RAP010-150 Installation Instructions Manual

Liquid chillers with puron refrigerant r-410a
Table of Contents

Advertisement

Table 15 — 30RAP Electrical Data — Dual Point, Optional Value Sound Fan, No Hydronic Package
UNIT VOLTAGE
UNIT
V-Hz
30RAP
(3 Ph)
208/230-3-60
380-3-60
070
380/415-3-50
460-3-60
575-3-60
208/230-3-60
380-3-60
080
380/415-3-50
460-3-60
575-3-60
208/230-3-60
380-3-60
090
380/415-3-50
460-3-60
575-3-60
208/230-3-60
380-3-60
100
380/415-3-50
460-3-60
575-3-60
208/230-3-60
380-3-60
115
380/415-3-50
460-3-60
575-3-60
208/230-3-60
380-3-60
130
380/415-3-50
460-3-60
575-3-60
208/230-3-60
380-3-60
150
380/415-3-50
460-3-60
575-3-60
LEGEND
ICF
— Instantaneous Current Flow
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to
the unit terminals is not below or above the listed minimum and maximum
limits. Maximum allowable phase imbalance is: voltage, 2%; amps 10%.
2. All units/modules have dual point primary power connection. (Each unit/
module requires its own power supply.) Main power must be supplied from
a field-supplied disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as
long as the power supply disconnect and heater safety device are on.
Supplied
MCA
MOCP
Min
Max
187
254
158.6
342
418
96.0
342
440
77.0
414
506
77.0
518
632
66.3
187
254
206.3
342
418
110.8
342
440
94.9
414
506
94.9
518
632
80.3
187
254
221.0
342
418
133.9
342
440
107.2
414
506
107.2
518
632
92.6
187
254
239.0
342
418
127.3
342
440
107.8
414
506
107.8
518
632
86.8
187
254
296.6
342
418
156.0
342
440
132.7
414
506
132.7
518
632
106.0
187
254
303.2
342
418
159.9
342
440
136.0
414
506
136.0
518
632
108.6
187
254
372.2
342
418
199.2
342
440
168.2
414
506
168.2
518
632
136.2
CIRCUIT 1
Rec
ICF
Fuse
Size
200
428.8
175
125
249.5
110
100
222.4
90
100
222.4
90
90
168.7
80
250
442.2
225
125
216.2
125
110
216.0
110
110
216.0
110
100
164.4
90
250
491.2
250
150
287.4
150
125
252.6
125
125
252.6
125
110
195.0
100
300
681.2
300
175
380.7
150
125
315.8
125
125
315.8
125
110
254.4
100
350
687.8
350
175
368.0
175
150
306.8
150
150
306.8
150
125
248.2
125
350
694.4
350
175
371.9
175
150
310.1
150
150
310.1
150
125
250.8
125
450
814.4
400
225
452.6
225
200
376.2
200
200
376.2
200
150
303.8
150
4. Power draw control circuits include both crankcase heaters (sizes 070-
150 only) and cooler heaters (where used). Each compressor on sizes
070-090 has a crankcase heater which draws 90 watts of power, while
each compressor on sizes 100-150 has a crankcase heater which draws
56 watts of power.
39
CIRCUIT 2
MCA
MOCP
ICF
181.4
225
451.6
110.5
125
264.0
87.4
110
232.8
87.4
110
232.8
77.0
100
179.4
181.4
225
451.6
110.5
125
264.0
87.4
110
232.8
87.4
110
232.8
77.0
100
179.4
181.4
225
451.6
110.5
125
264.0
87.4
110
232.8
87.4
110
232.8
77.0
100
179.4
243.8
300
635.0
124.8
150
336.8
106.3
125
280.4
106.3
125
280.4
85.2
110
227.4
243.8
300
635.0
124.8
150
336.8
106.3
125
280.4
106.3
125
280.4
85.2
110
227.4
306.2
400
748.4
160.2
200
413.6
135.2
175
343.2
135.2
175
343.2
110.2
125
277.8
306.2
400
748.4
160.2
200
413.6
135.2
175
343.2
135.2
175
343.2
110.2
125
277.8
Rec
Fuse
Size
200
125
100
100
90
200
125
100
100
90
200
125
100
100
90
300
150
125
125
100
300
150
125
125
100
350
175
150
150
125
350
175
150
150
125

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents