Maintenance After A Long Stop Period - Daikin RXYSCQ4TMV1B Installer And User Manual

Table of Contents

Advertisement

CAUTION
Pay attention to the fan.
It is dangerous to inspect the unit while the fan is running.
Be sure to turn off the main switch before executing any
maintenance task.
CAUTION
After a long use, check the unit stand and fitting for
damage. If damaged, the unit may fall and result in injury.
NOTICE
Do not wipe the controller operation panel with benzine,
thinner, chemical dust cloth, etc. The panel may get
discoloured or the coating peeled off. If it is heavily dirty,
soak a cloth in water-diluted neutral detergent, squeeze it
well and wipe the panel clean. Wipe it with another dry
cloth.
19.1
Maintenance after a long stop
period
E.g., at the beginning of the season.
▪ Check and remove everything that might be blocking inlet and
outlet vents of indoor units and outdoor units.
▪ Clean air filters and casings of indoor units. Contact your installer
or maintenance person to clean air filters and casings of the
indoor unit. Maintenance tips and procedures for cleaning are
provided in the installation/operation manuals of dedicated indoor
units. Make sure to install cleaned air filters back in the same
position.
▪ Turn on the power at least 6 hours before operating the unit in
order to ensure smoother operation. As soon as the power is
turned on, the user interface display appears.
19.2
Maintenance before a long stop
period
E.g., at the end of the season.
▪ Let the indoor units run in fan only operation for about half a day in
order to dry the interior of the units. Refer to
cooling, heating, fan only, and automatic operation"  on page  50
for details on fan only operation.
▪ Turn off the power. The user interface display disappears.
▪ Clean air filters and casings of indoor units. Contact your installer
or maintenance person to clean air filters and casings of the
indoor unit. Maintenance tips and procedures for cleaning are
provided in the installation/operation manuals of dedicated indoor
units. Make sure to install cleaned air filters back in the same
position.
19.3
About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent
gases into the atmosphere.
Refrigerant type: R410A
Global warming potential value: 2087.5
Periodical inspections for refrigerant leaks may be required
depending on the applicable legislation. Please contact your installer
for more information.
RXYSCQ4+5TMV1B
VRV IV-S system air conditioner
4P404224-1 – 2015.03
WARNING
The refrigerant in the air conditioner is safe and normally
does not leak. If the refrigerant leaks in the room, contact
with a fire of a burner, a heater or a cooker may result in a
harmful gas.
Turn off any combustible heating devices, ventilate the
room and contact the dealer where you purchased the unit.
Do not use the air conditioner until a service person
confirms that the portion where the refrigerant leaks is
repaired.
19.4
19.4.1
▪ This product includes a warranty card that was filled in by the
dealer at the time of installation. The completed card has to be
checked by the customer and stored carefully.
▪ If repairs to the air conditioner are necessary within the warranty
period, contact your dealer and keep the warranty card at hand.
19.4.2
Since dust collects when using the unit for several years,
performance of the unit will deteriorate to some extent. As taking
apart and cleaning interiors of units requires technical expertise and
in order to ensure the best possible maintenance of your units, we
recommend to enter into a maintenance and inspection contract on
top of normal maintenance activities. Our network of dealers has
access to a permanent stock of essential components in order to
keep your air conditioner in operation as long as possible. Contact
your dealer for more information.
When asking your dealer for an intervention, always state:
▪ The complete model name of the air conditioner.
▪ The manufacturing number (stated on the nameplate of the unit).
▪ The installation date.
▪ The symptoms or malfunction, and details of the defect.
WARNING
"17.2.2  About
▪ Do not modify, disassemble, remove, reinstall or repair
▪ In case of accidental refrigerant leaks, make sure there
19.4.3
Be aware that the mentioned maintenance and replacement cycles
do not relate to the warranty period of the components.
19 Maintenance and service
After-sales service and warranty
Warranty period
Recommended maintenance and
inspection
the unit yourself as incorrect dismantling or installation
may cause an electric shock or fire. Contact your
dealer.
are no naked flames. The refrigerant itself is entirely
safe, non-toxic and non-combustible, but it will
generate toxic gas when it accidentally leaks into a
room where combustible air from fan heaters, gas
cookers, etc. is present. Always have qualified service
personnel confirm that the point of leakage has been
repaired or corrected before resuming operation.
Recommended maintenance and
inspection cycles
Installer and user reference guide