To Use Mode 2; Mode 1 (And Default Situation): Monitoring Settings - Daikin RXYSCQ4TMV1B Installer And User Manual

Table of Contents

Advertisement

7 Configuration
Example: 7‑LEDs display – Default situation
You can read out the status of low noise operation as follows:
#
Action
1
Make sure the LEDs are
showing the default situation.
2
Check the status of LED
H6P.
Example: 7‑LEDs display – Mode 1
You can read out setting [1‑5] (=  the total number of connected
indoor units) as follows:
#
Action
1
Start from the default
situation.
2
Select mode 1.
3
Select setting 5.
("X×" depends on the setting
that you want to select.)
4
Display the value of setting 5.
(there are 8 indoor units
connected)
5
Quit mode 1.
7.2.6

To use mode 2

In mode 2 you can make field settings to configure the system.
Example: 7‑LEDs display – Mode 2
You can change the value of setting [2‑8] (=  T
during cooling operation) to 4 (= 8°C) as follows:
#
Action
1
Start from the default
situation.
2
Select mode 2.
3
Select setting 8.
("X×" depends on the setting
that you want to select.)
Installer and user reference guide
28
Button/display
(H1P OFF)
H6P OFF: Unit is currently
not operating under low noise
restrictions.
H6P ON: Unit is currently
operating under low noise
restrictions.
Button/display
BS1 [1×]
BS2 [X×]
(= binary 5)
BS3 [1×]
(= binary 8)
BS1 [1×]
target temperature
e
Button/display
BS1 [5 s]
BS2 [X×]
(= binary 8)
#
Action
4
Select value 4 (= 8°C).
a: Display the current value.
b: Change to 4. ("X×"
depends on the current
value, and the value that you
want to select.)
c: Enter the value in the
system.
d: Confirm. The system starts
operating according to the
setting.
5
Quit mode 2.
7.2.7
Mode 1 (and default situation): Monitoring
settings
In mode 1 (and in default situation) you can read out some
information.
7‑LEDs display – Default situation (H1P OFF)
You can read out the following information:
Value / Description
H6P
Shows the status of low noise operation.
OFF
Unit is currently not operating under low noise
restrictions.
ON
Unit is currently operating under low noise
restrictions.
Low noise operation reduces the sound generated by the
unit compared to nominal operating conditions.
Low noise operation can be set in mode 2. There are two
methods to activate low noise operation of the outdoor unit
system.
▪ The first method is to enable an automatic low noise
operation during night time by field setting. The unit will
operate at the selected low noise level during the
selected time frames.
▪ The second method is to enable low noise operation
based on an external input. For this operation an optional
accessory is required.
Button/display
a
BS3 [1×]
b
BS2 [X×]
c
BS3 [1×]
d
BS3 [1×]
BS1 [1×]
RXYSCQ4+5TMV1B
VRV IV-S system air conditioner
4P404224-1 – 2015.03

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxyscq5tmv1b

Table of Contents