Adjusting The Air Flow Direction - Daikin RXYSCQ4TMV1B Installer And User Manual

Table of Contents

Advertisement

Result: The operation lamp goes out and the system stops
operating.
NOTICE
Do not turn off power immediately after the unit stops, but
wait for at least 5 minutes.
17.4

Adjusting the air flow direction

Refer to the operation manual of the user interface.
17.4.1
About the air flow flap
Double flow+multi-flow units
Corner units
Ceiling suspended units
Wall-mounted units
For the following conditions, a micro computer controls the air flow
direction which may be different from the display.
Cooling
▪ When the room temperature is
lower
than
the
set
temperature.
▪ When operating continuously at horizontal air flow direction.
▪ When continuous operation with downward air flow is performed
at the time of cooling with a ceiling-suspended or a wall-mounted
unit, the micro computer may control the flow direction, and then
the user interface indication will also change.
The air flow direction can be adjusted in one of the following ways:
▪ The air flow flap itself adjusts its position.
▪ The air flow direction can be fixed by the user.
▪ Automatic
and desired position
WARNING
Never touch the air outlet or the horizontal blades while the
swing flap is in operation. Fingers may become caught or
the unit may break down.
NOTICE
▪ The movable limit of the flap is changeable. Contact
your dealer for details. (only for double-flow, multi-flow,
corner, ceiling-suspended and wall-mounted).
▪ Avoid operating in the horizontal direction
cause dew or dust to settle on the ceiling or flap.
RXYSCQ4+5TMV1B
VRV IV-S system air conditioner
4P404224-1 – 2015.03
Heating
▪ When starting operation.
▪ When the room temperature is
higher
than
the
set
temperature.
▪ At defrost operation.
.
. It may
17.5
Setting the master user interface
17.5.1
About setting the master user interface
a
b
c
c
f
d
d
a
VRV IV-S Heat pump outdoor unit
b
Refrigerant piping
c
VRV direct expansion (DX) indoor unit
d
User interface (dedicated depending on indoor unit type)
e
BP box (required to connect Residential Air (RA) or Sky Air
(SA) direct expansion (DX) indoor units)
f
Residential Air (RA) direct expansion (DX) indoor units
g
User interface (wireless, dedicated depending on indoor
unit type)
When the system is installed as shown in the figure above, it is
necessary to designate one of the user interfaces as the master user
interface.
The displays of slave user interfaces show
under centralised control) and slave user interfaces automatically
follow the operation mode directed by the master user interface.
Only the master user interface can select heating or cooling mode.
17.5.2
To designate the master user interface
(VRV DX)
In case only VRV  DX indoor units are connected to the VRV IV-S
system:
1 Press the operation mode selector button of the current master
user interface for 4 seconds. In case this procedure was not yet
performed, the procedure can be executed on the first user
interface operated.
Result: The display showing
centralised control) of all slave user interfaces connected to the
same outdoor unit flashes.
2 Press the operation mode selector button of the controller that
you wish to designate as the master user interface.
Result: Designation is completed. This user interface is
designated as the master user interface and the display
showing
(change-over
vanishes. The displays of other user interfaces show
(change-over under centralised control).
17.5.3
To designate the master user interface
(RA DX)
In case only RA  DX indoor units are connected to the VRV IV-S
system:
1 Stop all indoor units.
2 When the system is not operating (all indoor units thermo OFF),
you can define the master RA DX indoor unit by addressing that
unit with infrared user interface (instruct thermo ON in desired
mode).
The only way to change the master unit is by repeating the previous
procedure. A cool/heat switchover (or opposite) is only possible by
changing the operation mode of the defined master indoor unit.
17 Operation
e
e
f
g
g
(change-over
(change-over under
under
centralised
control)
Installer and user reference guide