Overview; C.5.1 Overview - GE N60 UR Series Instruction Manual

Network stability and synchrophasor measurement system
Table of Contents

Advertisement

APPENDIX C
C.5IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
The N60 can be configured for IEC 61850 via the EnerVista UR Setup software as follows.
1.
An ICD file is generated for the N60 by the EnerVista UR Setup software that describe the capabilities of the IED.
2.
The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven-
dors) for system configuration.
3.
The result is saved to a SCD file, which is then imported back to EnerVista UR Setup to create one or more settings
file(s). The settings file(s) can then be used to update the relay(s) with the new configuration information.
The configuration process is illustrated below.
Creating ICD (GE Multilin)
IED (UR-series)
OR
EnerVista
Setting files
UR Setup
(.URS)
System
specification data
System specification tool
Updating IED with new configuration (GE Multilin)
EnerVista UR Setup
URS 1
URS 2
Write settings file
Write settings
to other devices
file to device
UR relay 1
UR relay 2
The following acronyms and abbreviations are used in the procedures describing the IED configuration process for IEC
61850:
BDA: Basic Data Attribute, that is not structured
DAI: Instantiated Data Attribute
DO: Data Object type or instance, depending on the context
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUP
IEC 61850 related
Process of
configuration for the
creating ICD
IED (GSSE/GOOSE,
(vendor 2)
server, logical node
prefixes, MMXU
deadbands, GGIO2
control, etc.)
ICD file 2
ICD file 1
SSD file
Vendor specific tool
for updating new
configuration to IED
URS
(vendor 2)
Vendor relay 2
UR relay
Figure 0–1: IED CONFIGURATION PROCESS
Process of
creating ICD
(vendor 3)
ICD file 3
Import
System configurator
System Configuration
(network, cross-
communications, IED setting
modification, etc.)
SCD file
Vendor specific tool
for updating new
configuration to IED
(vendor 3)
Vendor relay 3
Ethernet

C.5.1 OVERVIEW

C
Process of
creating ICD
(vendor )
ICD file
Vendor specific tool
for updating new
configuration to IED
(vendor )
Vendor relay
842790A1.CDR