B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 15 of 54)
ADDR
REGISTER NAME
4707
Breaker 1 phase A / three-pole closed
4708
Breaker 1 phase B closed
4709
Breaker 1 phase C closed
470A
Breaker 1 external alarm
470B
Breaker 1 alarm delay
B
470D
Breaker 1 pushbutton control
470E
Breaker 1 manual close recall time
4710
Breaker 1 out of service
4711
Breaker 1 block open
4712
Breaker 1 block close
4713
Breaker 1 phase A / three-pole opened
4714
Breaker 1 phase B opened
4715
Breaker 1 phase C opened
4716
Breaker 1 operate time
4717
Breaker 1 events
4718
Reserved
4719
...Repeated for breaker 2
4732
...Repeated for breaker 3
474B
...Repeated for breaker 4
4764
...Repeated for breaker 5
477D
...Repeated for breaker 6
Synchrocheck (Read/Write Setting) (2 modules)
47A0
Synchrocheck 1 Function
47A1
Synchrocheck 1 V1 Source
47A2
Synchrocheck 1 V2 Source
47A3
Synchrocheck 1 Maximum Voltage Difference
47A5
Synchrocheck 1 Maximum Angle Difference
47A6
Synchrocheck 1 Maximum Frequency Difference
47A7
Synchrocheck 1 Dead Source Select
47A8
Synchrocheck 1 Dead V1 Maximum Voltage
47A9
Synchrocheck 1 Dead V2 Maximum Voltage
47AA
Synchrocheck 1 Live V1 Minimum Voltage
47AB
Synchrocheck 1 Live V2 Minimum Voltage
47AC
Synchrocheck 1 Target
47AD
Synchrocheck 1 Events
47AE
Synchrocheck 1 Block
47AF
Synchrocheck 1 Frequency Hysteresis
47B0
...Repeated for Synchrocheck 2
Demand (Read/Write Setting)
47D0
Demand Current Method
47D1
Demand Power Method
47D2
Demand Interval
47D3
Demand Input
Demand (Read/Write Command)
47D4
Demand Clear Record
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
4C0A
User-Definable Display 1 Bottom Line Text
4C14
Modbus Addresses of Display 1 Items (5 items)
4C19
Reserved (7 items)
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
B-22
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 1000000
s
0.001
0 to 1
---
0 to 1000000
s
0.001
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 2
s
0.001
0 to 1
---
---
---
---
0 to 1
---
0 to 5
---
0 to 5
---
0 to 400000
V
0 to 100
degrees
0 to 2
Hz
0.01
0 to 5
---
0 to 1.25
pu
0.01
0 to 1.25
pu
0.01
0 to 1.25
pu
0.01
0 to 1.25
pu
0.01
0 to 2
---
0 to 1
---
0 to 65535
---
0 to 0.1
Hz
0.01
0 to 2
---
0 to 2
---
0 to 5
---
0 to 65535
---
0 to 1
---
0 to 65535
---
---
---
---
---
---
---
0 to 65535
---
---
---
---
APPENDIX B
FORMAT
DEFAULT
1
F300
0
1
F300
0
1
F300
0
1
F300
0
F003
0
1
F102
0 (Disabled)
F003
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
1
F300
0
F001
70
1
F102
0 (Disabled)
---
---
1
F102
0 (Disabled)
1
F167
0 (SRC 1)
1
F167
1 (SRC 2)
1
F060
10000
1
F001
30
F001
100
1
F176
1 (LV1 and DV2)
F001
30
F001
30
F001
70
F001
70
1
F109
0 (Self-reset)
1
F102
0 (Disabled)
1
F300
0
F001
6
1
F139
0 (Thrm. Exponential)
1
F139
0 (Thrm. Exponential)
1
F132
2 (15 MIN)
1
F300
0
1
F126
0 (No)
1
F001
0
F202
" "
F202
""
1
F001
0
F001
0