6 ACTUAL VALUES

6.4RECORDS

PATH: ACTUAL VALUES
RECORDS

EVENT RECORDS

MESSAGE
MESSAGE
MESSAGE
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological order
from most recent to oldest. If all 1024 event records have been filled, the oldest record will be removed as a new record is
added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated with the
event trigger. Refer to the
COMMANDS
PATH: ACTUAL VALUES
RECORDS

OSCILLOGRAPHY

MESSAGE
MESSAGE
MESSAGE
MESSAGE
This menu allows the user to view the number of triggers involved and number of oscillography traces available. The
value is calculated to account for the fixed amount of data storage for oscillography. See the Oscillog-
CYCLES PER RECORD
raphy section of chapter 5 for additional details.
A trigger can be forced here at any time by setting "Yes" to the
menu for information on clearing the oscillography records.
CLEAR RECORDS
PATH: ACTUAL VALUES
RECORDS

DATA LOGGER

MESSAGE
The
represents the time at which the oldest available samples were taken. It will be static until the log
OLDEST SAMPLE TIME
gets full, at which time it will start counting at the defined sampling rate. The
most recent samples were taken. It counts up at the defined sampling rate. If the data logger channels are defined, then
both values are static.
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
EVENT RECORDS
EVENT: XXXX
RESET OP(PUSHBUTTON)
EVENT: 3
POWER ON
EVENT: 2
POWER OFF
EVENT: 1
EVENTS CLEARED
menu for clearing event records.
CLEAR RECORDS
OSCILLOGRAPHY
FORCE TRIGGER?
No
NUMBER OF TRIGGERS:
0
AVAILABLE RECORDS:
0
CYCLES PER RECORD:
0.0
LAST CLEARED DATE:
2000/07/14
15:40:16
FORCE TRIGGER?
DATA LOGGER
OLDEST SAMPLE TIME:
2000/01/14 13:45:51
NEWEST SAMPLE TIME:
2000/01/14 15:21:19
6.4.1 EVENT RECORDS
EVENT 3
DATE: 2000/07/14
EVENT 3
TIME: 14:53:00.03405
Date and Time Stamps
6.4.2 OSCILLOGRAPHY
Range: No, Yes
command. Refer to the
6.4.3 DATA LOGGER
represents the time the
NEWEST SAMPLE TIME
6.4 RECORDS
6
COMMANDS
6-21

Advertisement

Table of Contents
loading