5.6 CONTROL ELEMENTS
PATH: SETTINGS
CONTROL ELEMENTS

TRIP BUS 1

5
The trip bus element allows aggregating outputs of protection and control elements without using FlexLogic™ and assign-
ing them a simple and effective manner. Each trip bus can be assigned for either trip or alarm actions. Simple trip condition-
ing such as latch, delay, and seal-in delay are available.
The easiest way to assign element outputs to a trip bus is through the EnerVista UR Setup software A protection summary
is displayed by navigating to a specific protection or control protection element and checking the desired bus box. Once the
desired element is selected for a specific bus, a list of element operate-type operands are displayed and can be assigned
to a trip bus. If more than one operate-type operand is required, it may be assigned directly from the trip bus menu.
5-164
TRIP BUS
TRIP BUS 1
FUNCTION: Disabled
TRIP BUS 1 BLOCK:
MESSAGE
Off
TRIP BUS 1 PICKUP
MESSAGE
DELAY:
TRIP BUS 1 RESET
MESSAGE
DELAY:
TRIP BUS 1 INPUT 1:
MESSAGE
Off
TRIP BUS 1 INPUT 2:
MESSAGE
Off
TRIP BUS 1 INPUT 16:
MESSAGE
Off
TRIP BUS 1
MESSAGE
LATCHING: Disabled
TRIP BUS 1 RESET:
MESSAGE
Off
TRIP BUS 1 TARGET:
MESSAGE
Self-reset
TRIP BUS 1
MESSAGE
EVENTS: Disabled
N60 Network Stability and Synchrophasor Measurement System
TRIP BUS 1(6)
Range: Enabled, Disabled
Range: FlexLogic™ operand
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Enabled, Disabled
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Enabled, Disabled
5 SETTINGS
5.6.14 TRIP BUS