GE N60 UR Series Instruction Manual page 196

Network stability and synchrophasor measurement system
Table of Contents

Advertisement

5.3 SYSTEM SETUP
SETTINGS
PMU 1 CURR TRIGGER
FUNCTION:
Enabled = 1
PMU 1 CURR TRIG BLK:
Off = 0
SETTINGS
PMU 1 SIGNAL
SOURCE:
IA
IB
IC
i) POWER TRIGGERING
PATH: SETTINGS
SYSTEM SETUP
PMU 1 POWER
TRIGGER
5
This element responds to abnormal power. Separate thresholds are provided for active, reactive, and apparent powers. In
terms of signaling its operation the element does not differentiate between the three types of power. The trigger responds to
the single-phase and three-phase power signals of the phasor measurement unit (PMU) source.
PMU 1 POWER TRIGGER ACTIVE: This setting specifies the pickup threshold for the active power of the source. For
single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal secondary voltage,
the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a single-phase
power. The comparator applies a 3% hysteresis.
PMU 1 POWER TRIGGER REACTIVE: This setting specifies the pickup threshold for the reactive power of the
source. For single-phase power, 1 pu is a product of 1 pu voltage and 1 pu current, or the product of nominal second-
ary voltage, the VT ratio and the nominal primary current. For the three-phase power, 1 pu is three times that for a sin-
gle-phase power. The comparator applies a 3% hysteresis.
5-82
SETTINGS
PMU 1 CURR TRIGGER PICKUP:
RUN
I > PICKUP
I > PICKUP
I > PICKUP
Figure 5–26: CURRENT TRIGGER SCHEME LOGIC
PHASOR MEASUREMENT...
PMU 1 POWER TRIGGER
FUNCTION: Disabled
PMU 1 POWER TRIGGER
MESSAGE
ACTIVE: 1.250 pu
PMU 1 POWER TRIGGER
MESSAGE
REACTIVE: 1.250 pu
PMU 1 POWER TRIGGER
MESSAGE
APPARENT: 1.250 pu
PMU 1 POWER TRIGGER
MESSAGE
PKP TIME: 0.10 s
PMU 1 POWER TRIGGER
MESSAGE
DPO TIME: 1.00 s
PMU 1 PWR TRIG BLK:
MESSAGE
Off
PMU 1 POWER TRIGGER
MESSAGE
TARGET: Self-Reset
PMU 1 POWER TRIGGER
MESSAGE
EVENTS: Disabled
N60 Network Stability and Synchrophasor Measurement System
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 POWER TRIGGER
PMU 1 ROCOF TRIGGER
SETTING
PMU 1 USER TRIGGER:
Off = 0
SETTINGS
to STAT bits of
PMU 1 CURR TRIGGER PKP TIME:
the data frame
PMU 1 CURR TRIGGER DPO TIME:
t
PKP
t
DPO
PMU 1 TRIGGERING
PMU 1 POWER TRIGGER
Range: Enabled, Disabled
Range: 0.250 to 3.000 pu in steps of 0.001
Range: 0.250 to 3.000 pu in steps of 0.001
Range: 0.250 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic™ operand
Range: Self-Reset, Latched, Disabled
Range: Enabled, Disabled
5 SETTINGS
FLEXLOGIC OPERAND
PMU 1 TRIGGERED
FLEXLOGIC OPERAND
PMU 1 CURR TRIGGER
847000A1.CDR
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents