GE N60 UR Series Instruction Manual page 385

Network stability and synchrophasor measurement system
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 20 of 54)
ADDR
REGISTER NAME
65D4
Power Swing Detect Event
65D5
Power Swing Detect Shape
65D6
Power Swing Detect Quad Forward Middle
65D7
Power Swing Detect Quad Forward Outer
65D8
Power Swing Detect Quad Reverse Middle
65D9
Power Swing Detect Quad Reverse Outer
65DA
Power Swing Detect Outer Right Blinder
65DB
Power Swing Detect Outer Left Blinder
65DC
Power Swing Detect Middle Right Blinder
65DD
Power Swing Detect Middle Left Blinder
65DE
Power Swing Detect Inner Right Blinder
65DF
Power Swing Detect Inner Left Blinder
Sensitive Directional Power (Read/Write Grouped Setting) (2 modules)
66A0
Sensitive Directional Power 1 Function
66A1
Sensitive Directional Power 1 Signal Source
66A2
Sensitive Directional Power 1 RCA
66A3
Sensitive Directional Power 1 Calibration
66A4
Sensitive Directional Power 1 STG1 SMIN
66A5
Sensitive Directional Power 1 STG1 Delay
66A6
Sensitive Directional Power 1 STG2 SMIN
66A7
Sensitive Directional Power 1 STG2 Delay
66A8
Sensitive Directional Power 1 Block
66A9
Sensitive Directional Power 1 Target
66AA
Sensitive Directional Power 1 Events
66AB
Reserved (5 items)
66B0
...Repeated for Sensitive Directional Power 2
Phase Undervoltage (Read/Write Grouped Setting) (2 modules)
7000
Phase Undervoltage 1 Function
7001
Phase Undervoltage 1 Signal Source
7002
Phase Undervoltage 1 Pickup
7003
Phase Undervoltage 1 Curve
7004
Phase Undervoltage 1 Delay
7005
Phase Undervoltage 1 Minimum Voltage
7006
Phase Undervoltage 1 Block
7007
Phase Undervoltage 1 Target
7008
Phase Undervoltage 1 Events
7009
Phase Undervoltage 1 Measurement Mode
700A
Reserved (6 items)
7013
...Repeated for Phase Undervoltage 2
Phase Overvoltage (Read/Write Grouped Setting)
7040
Phase Overvoltage 1 Function
7041
Phase Overvoltage 1 Source
7042
Phase Overvoltage 1 Pickup
7043
Phase Overvoltage 1 Delay
7044
Phase Overvoltage 1 Reset Delay
7045
Phase Overvoltage 1 Block
7046
Phase Overvoltage 1 Target
7047
Phase Overvoltage 1 Events
7048
Reserved (8 items)
dcmA Inputs (Read/Write Setting) (24 modules)
7300
dcmA Inputs 1 Function
7301
dcmA Inputs 1 ID
7307
Reserved 1 (4 items)
730B
dcmA Inputs 1 Units
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
STEP
0 to 1
---
1
0 to 1
---
1
0.1 to 500
ohms
0.01
0.1 to 500
ohms
0.01
0.1 to 500
ohms
0.01
0.1 to 500
ohms
0.01
0.1 to 500
ohms
0.01
0.1 to 500
ohms
0.01
0.1 to 500
ohms
0.01
0.1 to 500
ohms
0.01
0.1 to 500
ohms
0.01
0.1 to 500
ohms
0.01
0 to 1
---
1
0 to 5
---
1
0 to 359
degrees
1
0 to 0.95
degrees
0.05
-1.2 to 1.2
pu
0.001
0 to 600
s
0.01
-1.2 to 1.2
pu
0.001
0 to 600
s
0.01
---
---
---
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
0 to 1
---
1
0 to 5
---
1
0 to 3
pu
0.001
0 to 1
---
1
0 to 600
s
0.01
0 to 3
pu
0.001
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 3
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
0 to 65535
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
---
---
---
0 to 65535
---
1
---
---
---
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F102
0 (Disabled)
F085
0 (Mho Shape)
F001
6000
F001
7000
F001
6000
F001
7000
F001
10000
F001
10000
F001
10000
F001
10000
F001
10000
F001
10000
F102
0 (Disabled)
F167
0 (SRC 1)
F001
0
F001
0
F002
100
F001
50
F002
100
F001
2000
F001
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F001
1000
F111
0 (Definite Time)
F001
100
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F186
0 (Phase to Ground)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F001
1000
F001
100
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F205
"DCMA I 1"
F001
0
F206
"mA"