5
Dimensional drawing & centre of gravity

5 - 1 Dimensional drawing

FXFQ20,25,32,40,50,63P
950
Piping side
Drain side
VIEW A
840
55
340
Hanging bolt
4 x M8~M10
NOTES
1
Location of the nameplates
- Unit body: on the control box cover.
- Decoration panel: on the panel frame at the motor side under the corner cover
2
When installing an optional accessory, refer to the installation drawings.
- For the fresh air intake kit an inspection port is necessary
3
In case of using an infrared remote control, this position will be a signal
receiver. Refer to the drawing of the infrared remote control for more detail.
FXFQ80,100P
950
Piping side
Drain side
VIEW A
840
55
340
Hanging bolt
4 x M8~M10
NOTES
1
Location of the nameplates
- Unit body: on the control box cover.
- Decoration panel: on the panel frame at the motor side under the corner cover
2
When installing an optional accessory, refer to the installation drawings.
- For the fresh air intake kit an inspection port is necessary
3
In case of using an infrared remote control, this position will be a signal
receiver. Refer to the drawing of the infrared remote control for more detail.
12
• Indoor Units • ROUNDFLOW CASSETTE • FXFQ-P7VEB
860-910 (Ceiling opening)
300 or less
710 (Suspension position
420
3
SEE NOTE
420
55
55
35
280
330
SEE NOTE
4
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. MAX ceiling opening: 910mm.
5
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air
is inducted into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
6
Please respect the distances as shown on the figure
860-910 (Ceiling opening)
300 or less
710 (Suspension position
420
3
SEE NOTE
420
55
55
35
280
330
SEE NOTE
4
Make sure the spacing between the ceiling and the cassette is no more
than 35mm. MAX ceiling opening: 910mm.
5
When the conditions exceed 30°C and RH 80% in the ceiling or fresh air
is inducted into the ceiling, an additional insulation is required
(polyethylene foam, thickness 10mm or more).
6
Please respect the distances as shown on the figure
®
• VRV Systems
• Indoor Units
SEE NOTE
840
55
35
4
4
SEE NOTE
SEE NOTE
840
55
35
4
4
SEE NOTE
Nr
Name
4
1
Liquid pipe connection
2
Gas pipe connection
3
Drain pipe connection
VP25 (O.D. ø 32 /I.D. ø 25)
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
10
Knock out hole
MODEL
213
FXFQ20-50P
FXFQ63P
VIEW B
VENTILATOR
EXTERNAL
6
SEE NOTE
SURFACE
LIGHT
1500 or more
2000 or more
4000 or more
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
(*) In case a discharge opening is closed with the 'sealing member' option,
the distance of 1500mm can be reduced to 500mm on the closed side.
Nr
Name
1
Liquid pipe connection
2
Gas pipe connection
4
3
Drain pipe connection
4
Power supply entry hole
5
Transmission wiring entry hole
6
Air discharge opening
7
Air suction grille
8
Corner decoration cover
9
Drain hose
10
Knock out hole
213
VIEW B
VENTILATOR
EXTERNAL
6
SEE NOTE
SURFACE
LIGHT
1500 or more
2000 or more
4000 or more
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
200mm
or more
1500mm
or more (*)
(*) In case a discharge opening is closed with the 'sealing member' option,
the distance of 1500mm can be reduced to 500mm on the closed side.
Description
ø A flare connection
ø B flare connection
O.D. ø 32 /I.D. ø 26
A
B
6.35
12.7
9.52
15.9
OTHER UNIT
1500mm
or more (*)
3TW28834-1B
Description
ø 9.52 flare connection
ø 15.90 flare connection
VP25 (O.D. ø 32 /I.D. ø 25)
O.D. ø 32 /I.D. ø 26
OTHER UNIT
1500mm
or more (*)
3TW28894-1B