1-2 ELECTRICAL SPECIFICATIONS

Power Supply
Name
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps (MFA) A
Full load amps (FLA)
Voltage range
Minimum
Maximum
Notes
1-2 ELECTRICAL SPECIFICATIONS
Power Supply
Name
Frequency
Voltage
Current
Minimum circuit amps
(MCA)
Maximum fuse amps (MFA) A
Full load amps (FLA)
Voltage range
Minimum
Maximum
Notes
• Indoor Units • ROUNDFLOW CASSETTE • FXFQ-P7VEB
FXFQ20P7VEB
Hz
V
A
0.4
16
A
0.3
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
Maximum allowable voltage range variation between phases is 2%.
FXFQ63P7VEB
Hz
V
A
0.9
16
A
0.7
V
V
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
Maximum allowable voltage range variation between phases is 2%.
®
• VRV Systems
• Indoor Units
FXFQ25P7VEB
FXFQ32P7VEB
VE
50/60
220-240/220
0.4
0.4
16
16
0.3
0.3
-10%
+10%
or above listed range limits.
MCA/MFA : MCA = 1.25 x FLA
MFA <= 4 x FLA
next lower standard fuse rating minimum 16A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
FXFQ80P7VEB
FXFQ100P7VEB
VE
50/60
220-240/220
0.9
16
0.7
-10%
+10%
or above listed range limits.
MCA/MFA : MCA = 1.25 x FLA
MFA <= 4 x FLA
next lower standard fuse rating minimum 16A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
FXFQ40P7VEB
FXFQ50P7VEB
0.5
0.6
16
16
0.4
0.5
FXFQ125P7VEB
1.4
1.9
16
16
1.1
1.5
5