Default Front Panel Display Screens
Page 170
This screen displays the kWh delivered values for each TOU rate in the previous
billing period.
N
OTE
PB = Previous Billing period. A billing period is the time between two consecutive meter readings for
billing purposes by a utility.
27 - 34. Prev Billing Peak Demand
These screens display the maximum kW delivered value for each TOU rate in
the previous billing period. These values result from Sliding Window (Rolling
Block) demand calculations.
35. Previous Season Energy
This screen displays the kWh delivered for each TOU rate in the previous billing
season. These values result from Sliding Window (Rolling Block) demand
calculations.
N
OTE
PS = Previous Season. Billing Seasons are defined in the TOU module description in the
ION Reference.
36 - 43. Prev Season Peak Demand
These screens display the maximum kW delivered for each TOU rate in the
previous billing season.
44. Prev Billing/Season Energy
These screens display the kWh delivered and received values in the previous
billing period and billing season.
45, 46. Prev Bill/ Season Pk Demand
These screens show the maximum kW sd received values in the previous billing
period and billing season. These values result from a Sliding Window (Rolling
Block) demand calculation.
47. Prev Billing/Season Energy
These screens display the kVARh delivered and received values in the previous
billing period and billing season.
48, 49. Prev Bill/Season Pk Demand
These screens display the kVAR delivered and received values in the previous
billing period and billing season. These values result from a Sliding Window
(Rolling Block) demand calculation.
50. Prev Billing/Season Energy
These screens display the kVAh delivered and received values in the previous
billing period and billing season.
51, 52. Prev Bill/Season Pk Demand
These screens display the kVA delivered and received values in the previous
billing period and billing season. These values result from a Sliding Window
(Rolling Block) demand calculation.