5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
FAULT REPORT 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The F60 relay supports one fault report and an associated fault locator. The signal source and trigger condition, as well as
the characteristics of the line or feeder, are entered in this menu.
The fault report stores data, in non-volatile memory, pertinent to an event when triggered. The captured data contained in
the FaultReport.txt file includes:
Fault report number
Name of the relay, programmed by the user
Firmware revision of the relay
Date and time of trigger
Name of trigger (specific operand)
Line/feeder ID via the name of a configured signal source
Active setting group at the time of trigger
Pre-fault current and voltage phasors (two cycles before either a 50DD disturbance associated with fault report source
or the trigger operate)
Fault current and voltage phasors (one cycle after the trigger)
Elements operated at the time of triggering
Events: 9 before trigger and 7 after trigger (only available via the relay webpage)
Fault duration times for each breaker (created by the breaker arcing current feature)
GE Multilin

FAULT REPORTS

FAULT REPORT 1
FAULT REPORT 1
SOURCE: SRC 1
FAULT REPORT 1 TRIG:
Off
FAULT REPORT 1 Z1
MAG: 3.00 Ω
FAULT REPORT 1 Z1
ANGLE: 75°
FAULT REPORT 1 Z0
MAG: 9.00 Ω
FAULT REPORT 1 Z0
ANGLE: 75°
FAULT REPORT 1 LINE
LENGTH UNITS: km
FAULT REP 1 LENGTH
(km
): 100.0
FAULT REPORT 1 VT
SUBSTITUTION: None
FAULT REP 1 SYSTEM
Z0 MAG: 2.00 Ω
FAULT REP 1 SYSTEM
Z0 ANGLE: 75°
F60 Feeder Protection System
5.2 PRODUCT SETUP
5.2.7 FAULT REPORTS
Range: SRC 1, SRC 2
Range: FlexLogic™ operand
Range: 0.01 to 250.00 ohms in steps of 0.01
Range: 25 to 90° in steps of 1
Range: 0.01 to 650.00 ohms in steps of 0.01
Range: 25 to 90° in steps of 1
Range: km, miles
Range: 0.0 to 2000.0 in steps of 0.1
Range: None, I0, V0
Range: 0.01 to 650.00 ohms in steps of 0.01
Range: 25 to 90° in steps of 1