Advertisement

5.4 FLEXLOGIC™
Table 5–7: F60 FLEXLOGIC™ OPERANDS (Sheet 3 of 8)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT
FREQ RATE 1 PKP
Frequency rate of
FREQ RATE 1 DPO
change
FREQ RATE 1 OP
FREQ RATE 2 to FREQ RATE 4
ELEMENT:
FxE 1 PKP
FlexElements™
FxE 1 OP
FxE 1 DPO
FxE 2 to FxE 8
ELEMENT:
GROUND IOC1 PKP
Ground
GROUND IOC1 OP
instantaneous
GROUND IOC1 DPO
overcurrent
GROUND IOC2
ELEMENT:
GROUND TOC1 PKP
Ground time
GROUND TOC1 OP
overcurrent
GROUND TOC1 DPO
GROUND TOC2
ELEMENT
HI-Z ARC DETECTED
High impedance
HI-Z ARC DETECTED-A
fault detection
HI-Z ARC DETECTED-B
(Hi-Z)
HI-Z ARC DETECTED-C
HI-Z ARC DETECTED-N
HI-Z ARC DETECTED DPO
HI-Z ARMED
HI-Z DISARMED
HI-Z DOWNED COND
HI-Z DOWNED COND-A
5
HI-Z DOWNED COND-B
HI-Z DOWNED COND-C
HI-Z DOWNED COND-N
HI-Z ARC SUSPECTED
HI-Z ARC SUSPECTED-A
HI-Z ARC SUSPECTED-B
HI-Z ARC SUSPECTED-C
HI-Z ARC SUSPECTED-N
HI-Z IOC A
HI-Z IOC B
HI-Z IOC C
HI-Z LOSS OF LOAD-A
HI-Z LOSS OF LOAD-B
HI-Z LOSS OF LOAD-C
ELEMENT:
INCIPNT FLT 1 OP
Incipient cable fault
INCIPNT FLT 1 OP A
detection
INCIPNT FLT 1 OP B
INCIPNT FLT 1 OP C
INCIPNT FLT 1 PKP
INCIPNT FLT 1 PKP A
INCIPNT FLT 1 PKP B
INCIPNT FLT 1 PKP C
INCIPNT FLT 2...
ELEMENT
LATCH 1 ON
Non-volatile latches
LATCH 1 OFF
LATCH 2 to LATCH 16
ELEMENT:
LOAD ENCHR PKP
Load encroachment
LOAD ENCHR OP
LOAD ENCHR DPO
ELEMENT:
NEG SEQ DIR OC1 FWD
Negative-sequence
NEG SEQ DIR OC1 REV
directional
NEG SEQ DIR OC2 FWD
overcurrent
NEG SEQ DIR OC2 REV
ELEMENT:
NEG SEQ IOC1 PKP
Negative-sequence
NEG SEQ IOC1 OP
instantaneous
NEG SEQ IOC1 DPO
overcurrent
NEG SEQ IOC2
5-88
OPERAND DESCRIPTION
The frequency rate of change 1 element has picked up
The frequency rate of change 1 element has dropped out
The frequency rate of change 1 element has operated
Same set of operands as shown for FREQ RATE 1
FlexElement™ 1 has picked up
FlexElement™ 1 has operated
FlexElement™ 1 has dropped out
Same set of operands as shown for FxE 1
Ground instantaneous overcurrent 1 has picked up
Ground instantaneous overcurrent 1 has operated
Ground instantaneous overcurrent 1 has dropped out
Same set of operands as shown for GROUND IOC 1
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
Same set of operands as shown for GROUND TOC1
The high impedance fault detection element has operated
The high impedance fault detection phase A element has operated
The high impedance fault detection phase B element has operated
The high impedance fault detection phase C element has operated
The high impedance fault detection neutral element has operated
No arcing has been detected
The high impedance fault detection element is in the armed state
The high impedance fault detection element is in the disarmed state
The high impedance fault downed conductor element has operated
The high impedance fault downed conductor phase A element has operated
The high impedance fault downed conductor phase B element has operated
The high impedance fault downed conductor phase C element has operated
The high impedance fault downed conductor neutral element has operated
The high impedance fault detection arcing suspected element has operated
The high impedance fault arcing suspected phase A element has operated
The high impedance fault arcing suspected phase B element has operated
The high impedance fault arcing suspected phase C element has operated
The high impedance fault arcing suspected neutral element has operated
The high impedance instantaneous overcurrent A element has operated
The high impedance instantaneous overcurrent B element has operated
The high impedance instantaneous overcurrent C element has operated
The high impedance fault phase A loss of load element has operated
The high impedance fault phase B loss of load element has operated
The high impedance fault phase C loss of load element has operated
Asserted when incipient cable fault detector 1 operates in any phase
Asserted when incipient cable fault detector 1 operates in phase A
Asserted when incipient cable fault detector 1 operates in phase B
Asserted when incipient cable fault detector 1 operates in phase C
Asserted when incipient cable fault detector 1 picks up in any phase
Asserted when incipient cable fault detector 1 picks up in phase A
Asserted when incipient cable fault detector 1 picks up in phase B
Asserted when incipient cable fault detector 1 picks up in phase C
Same set of operands as shown for INCIPNT FLT 1
Non-volatile latch 1 is ON (Logic = 1)
Non-voltage latch 1 is OFF (Logic = 0)
Same set of operands as shown for LATCH 1
Load encroachment has picked up
Load encroachment has operated
Load encroachment has dropped out
Negative-sequence directional overcurrent 1 forward has operated
Negative-sequence directional overcurrent 1 reverse has operated
Negative-sequence directional overcurrent 1 forward has operated
Negative-sequence directional overcurrent 1 reverse has operated
Negative-sequence instantaneous overcurrent 1 has picked up
Negative-sequence instantaneous overcurrent 1 has operated
Negative-sequence instantaneous overcurrent 1 has dropped out
Same set of operands as shown for NEG SEQ IOC1
F60 Feeder Protection System
5 SETTINGS
GE Multilin