GE F60 UR Series Instruction Manual page 262

Feeder protection system
Hide thumbs Also See for F60 UR Series:
Table of Contents

Advertisement

5.5 GROUPED ELEMENTS
The positive-sequence restraint must be considered when testing for pick-up accuracy and response time (multiple of
pickup). The operating quantity depends on the way the test currents are injected into the relay:
Single-phase injection: I
Three-phase pure zero- or negative-sequence injection, respectively: I
The directional unit uses the negative-sequence current and voltage for fault direction discrimination.
The following table defines the negative-sequence directional overcurrent element.
OVERCURRENT UNIT
MODE
Negative-sequence
Zero-sequence
The negative-sequence voltage must be higher than the
value to be validated for use as a polarizing signal. If the polarizing signal is not validated neither forward nor reverse
LEVEL
indication is given. The following figure explains the usage of the voltage polarized directional unit of the element.
The figure below shows the phase angle comparator characteristics for a phase A to ground fault, with settings of:
ECA
= 75° (element characteristic angle = centerline of operating characteristic)
FWD LA
= 80° (forward limit angle = ± the angular limit with the ECA for operation)
REV LA
= 80° (reverse limit angle = ± the angular limit with the ECA for operation)
The element incorporates a current reversal logic: if the reverse direction is indicated for at least 1.25 of a power system
5
cycle, the prospective forward indication will be delayed by 1.5 of a power system cycle. The element is designed to emu-
late an electromechanical directional device. Larger operating and polarizing signals will result in faster directional discrimi-
nation bringing more security to the element operation.
The forward-looking function is designed to be more secure as compared to the reverse-looking function, and therefore
should be used for the tripping direction. The reverse-looking function is designed to be faster as compared to the forward-
looking function and should be used for the blocking direction. This allows for better protection coordination. The above
bias should be taken into account when using the negative-sequence directional overcurrent element to directionalize other
protection elements.
5-136
= 1/3 × (1 – K) × I
op
injected
OPERATING CURRENT
= |I_2| – K × I_1|
I
op
= |I_0| – K × |I_1|
I
op
REV
LA
REV Operating
Region
LA
–I_2 line
–ECA line
LA
VCG
Figure 5–64: NEGATIVE-SEQUENCE DIRECTIONAL CHARACTERISTIC
F60 Feeder Protection System
.
= I
op
injected
DIRECTIONAL UNIT
DIRECTION
–V_2 + Z_offset × I_2
Forward
–V_2 + Z_offset × I_2
Reverse
–V_2 + Z_offset × I_2
Forward
–V_2 + Z_offset × I_2
Reverse
PRODUCT SETUP
DISPLAY PROPERTIES
–V_2 line
FWD
VAG (reference)
LA
LA
ECA
LA
REV
FWD
LA
LA
V_2 line
5 SETTINGS
.
COMPARED PHASORS
I_2 × 1∠ECA
–(I_2 × 1∠ECA)
I_2 × 1∠ECA
–(I_2 × 1∠ECA)
VOLTAGE CUT-OFF
ECA line
I_2 line
FWD Operating
Region
VBG
827806A2.CDR
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents