Drain Joint Installation; Notes On Drilling Hole On Wall; When Selecting A 24K Indoor Unit - Pioneer YN020GMFI22M2D Installation Manual

Dc inverter two,three,four and five zone multi split-type air conditioner heat pump
Hide thumbs Also See for YN020GMFI22M2D:
Table of Contents

Advertisement

NOTE: The minimum distance between the
outdoor unit and walls described in the
installation guide does not apply to airtight
rooms. Be sure to keep the unit unobstructed
in at least two of the three directions (M, N, P)
(See Fig. 6.7)
M
N
Fig. 6.7

Drain Joint Installation

Before bolting the outdoor unit in place, you
must install the drain joint at the bottom of the
unit. (See Fig. 6.8)
1. Fit the rubber seal on the end of the drain
joint that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the
base pan of the unit.
3. Rotate the drain joint 90° until it clicks in
place facing toward the front of the unit.
4. Connect a drain hose extension (not
included) to the drain joint to redirect water
from the unit during heating mode.
NOTE: Make sure the water drains to a safe
location where it will not cause water damage
or a slipping hazard.
Seal
Seal
Drain joint
(A)
Fig. 6.8
P
Base pan hole of
outdoor unit
(B)
Notes On Drilling hole on the wall
You must drill a hole into the wall for the
refrigerant piping, and the signal cable that will
connect the indoor and outdoor units.
1. Determine the location of the wall hole
based on the location of the outdoor unit.
2. Using a 65-mm (2.5") core drill, drill a hole
in the wall.
NOTE: When drilling the wall hole, make
sure to avoid wires, plumbing, and other
sensitive components.
3. Place the protective wall sleeve in the hole.
This protects the edges of the hole and will
help seal it when you finish the installation
process.

When Selecting a 24K Indoor Unit

The one 24K indoor unit can only be connected to
circuit A. If there are two 24K indoor units, they
can be connected to circuits A and B only.
(See Fig. 6.9)
Table 6.2: Connecting pipe sizes of indoor units.
(unit: inch)
Indoor Unit capacity
(Btu/h)
9K/12K
12K/18K
24K
Fig. 6.9
Liquid
Gas
1/4
3/8
1/4
1/2
3/8
5/8
Page 11