Pioneer YN020GMFI22M2D Installation Manual page 20

Dc inverter two,three,four and five zone multi split-type air conditioner heat pump
Hide thumbs Also See for YN020GMFI22M2D:
Table of Contents

Advertisement

1. Completely tighten ALL brass flare nuts, which
connect the ends of copper refrigerant lines to the
attached indoor units and the circuit service valves
on the outdoor unit, using proper torque.
2. Assure that both the 2-way (Liquid) and 3-way
(Gas) valves for each circuit at the outdoor unit
STAY CLOSED as they arrived originally.
3. Connect the low pressure hose on your gauge
manifold (usually blue) to the 3-way (Gas) valve's
service port, belonging to circuit A. Note: If there
is only one indoor unit it should be connected to
circuit A as the primary.
4. If the manifold gauge set's hoses have 1/4" SAE
onnections, a 1/4" to 5/16" SAE port adapter will be
needed. (Sold separately).
5. Connect the center hose of the gauge manifold
usually yellow) to the vacuum pump.
6. Fully open the Low side valve on the low pressure
side of your gauge manifold. Assure that the High
side valve on the high pressure side of your gauge
manifold stays closed.
7. Start the vacuum pump and operate according
to pump manufacturer's specifications. If your
vacuum pump has a valve, open it as well.
9. If the proper vacuum cannot be achieved within
30 minutes, the vacuum pump should be kept
running for an additional 15 minutes. If after the
additional 15 minutes of operation, the vacuum
still cannot be achieved, there could be a leak at
one or more of the flare pipe connections at either
end of a refrigerant pipes. Leak must be located
and the leaking nut must be tightened properly
before re-vacuuming the circuit.
10. If the vacuum is achieved, close the low side valve
at the low pressure side on your gauge manifold first
and shut the vacuum pump off. Leave the gauge
manifold set and the hoses connected and recheck
the vacuum reading 15 minutes later to assure there
is no vacuum loss. (Very small increase in vacuum
level is normal).
11. Circuit A is now dry and free of contaminants.
Do not remove the hose of your gauge manifold set
from the service port.
12. Remove the 2-way (Liquid) Valve's brass dust cap
of circuit A. Insert proper size Allen wrench into the
valve core and turn it counter clockwise for 1 turn,
wait for 3 seconds and quickly close the valve by
turning it in reverse direction. Check your low pressure
gauge on the manifold to assure it now indicates
positive pressure of approximately 80 to 120 PSI in
your lines.
Flare nut
Valve body
Valve stem
13. Apply soap-water mixture on both the indoor unit
connections and the outdoor unit connections for
circuit A with a soft brush to check for leakage at the
connecting points of the piping. If you notice air
bubbles, the specific connector has leakage and must
be tightened to stop the leakage. (An electronic leak
detector will be more efficient to use for this if available).
14. Re-insert proper size Allen wrench into the valve
core of the Liquid Valve (2 way) valve for circuit A and
turn it counter clockwise until it is fully back seated.
Do not force it, once it stops turning. Repeat the leak
checking procedure entirely at all connections of
circuit A. If you find a new leak, close the 2-way (Liquid)
valve you just opened first and tighten the flare nut
at the leaking connection until the leak is sealed.
Reopen the 2-way (Liquid) valve and check again.
15. Remove the 3-way (Gas) Valve's dust cap for circuit A.
Insert proper size Allen wrench into the valve core and
turn it counter clockwise until it is fully back seated.
Do not force it, once it stops turning.
2-way (Liquid) Valve
Cap
Page 20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Yn030gmfi22m3dYn040gmfi22m4dYn050gmfi22m5d

Table of Contents