Installation; Service Space - Daikin Altherma ERHQ006-008AD Technical Data Manual

Table of Contents

Advertisement

9

Installation

9 - 1 Service space

EBLQ011-016AA6W1
A. Non stacked installation
B. Stacked installation
1. Obstacles exist in front of the outlet side
C. Multiple-row installation
1. Installation of one unit per row
• Monobloc • EBLQ011-016AA6W1
Do not stack more than one unit.
About 100mm is required as the dimension for laying the upper outdoor unit's drain pipe.
Get the portion A sealed so that air from the outlet does not bypass.
Relation of dimensions of H, A, and L are shown in the
table below.
L
0 < L ≤ 1/2 H
L ≤ H
1/2 H < L
H < L
Installation impossible
TM
• Altherma
• Monobloc
2. Obstacles exist in front of the air inlet
2. Installing multiple units (2 units or more) in lateral
connection per row
A
150 (250)
200 (300)
Legend
Unit: mm
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
In these cases, close the bottom of
1
the installation frame to prevent
discharged air from being
bypassed.
2
In these cases, only 2 units can be
installed.
This situation is not allowed.
Figures between ( ) indicate the dimensions
only for the 100-125-140 class models.
3TW26739-4
3
9
233