6-2-5. Night operation (sound reduction) Control

Model name : TCB-PCMO4E
SW1: Night time signal switch
Operation
This function decreases noise at night or other times as necessary.
Terminal
ON
OFF
COOL
(SW1)
ON
OFF
The input signal is recognized during its rising/falling phase.
(After reaching the top/bottom of the rising/falling edge, the signal must remain there for at least 100 ms.)
The optional P.C. board should be connected to the header outdoor unit (U1).
The system's capacity is reduced during low-noise operation.
The table below provides a rough guide to this capacity reduction.
Model
During low-noise mode*
MMY-
MAP0806*
MAP1006*
MAP1206*
MAP1406*
MAP1606*
MAP1806*
MAP2006*
* Position of noise measuring device: 1 m from the front face of the set and 1.5 m above ground (in anechoic chambers)
Header outdoor unit
Connection
Outdoor unit
cable
interface PCB
C
N
5
0
8
Input signal
Operation
Night time control
Normal operation
dB(A)
Cooling
50
approx. 85%
50
approx. 70%
53
approx. 60%
53
approx. 80%
54
approx. 70%
54
approx. 65%
54
approx. 60%
Locally procured
Optional PCB
TB1
COM
P
J
1
7
COOL
HEAT
Shield
wire
Capacity
Heating
approx. 80%
approx. 65%
approx. 55%
approx. 80%
approx. 70%
approx. 65%
approx. 60%
− 89 −
SW1
Relative to maximum capacity