Toshiba MMY-MAP1006FT8(J)P-E Service Manual page 166

Super heat recovery multi-e (multi type) outdoor unit
Hide thumbs Also See for MMY-MAP1006FT8(J)P-E:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
E18
00:
No header unit
02:
Two or more header units
E19
E19
01:
Connection of outdoor unit
from other line
E20
E20
02:
Connection of indoor unit
from other line
E23
E23
E25
E25
Address of outdoor unit from
which signal is not received
normally
E26
E26
Detected outdoor unit No.
E28
E28
Location
of
Description
System status
detection
Indoor
Trouble in
Stop of
unit
communication
corresponding
between indoor
unit
header and
follower units
I/F
Trouble in
All stop
number of
outdoor header
units
I/F
Connection to
All stop
other line found
during
automatic
address setting
I/F
Outdoor-
All stop
outdoor
communication
transmission
trouble
I/F
Duplicated
All stop
follower outdoor
address
I/F
Signal lack of
All stop
outdoor unit
I/F
Outdoor
All stop
follower unit
trouble
− 165 −
Check code detection
Check items (locations)
condition(s)
Periodic communication
• Check remote controller
between indoor header and
wiring.
follower units cannot be
• Check indoor power supply
maintained.
wiring.
• Check P.C. boards of
indoor units.
• There are more than one
Outdoor header unit is
outdoor header units in
outdoor unit to which indoor-
one line.
outdoor tie cable (U1,U2) is
• There is no outdoor header
connected.
unit in one line.
• Check connection of
indoor-outdoor
communication line.
• Check for defect in outdoor
P.C. board (I/F).
Equipment from other line is
Disconnect inter-line tie cable
found to have been
in accordance with automatic
connected when indoor
address setting method
automatic address setting is
explained in "Address
in progress.
setting" section.
Signal cannot be transmitted
• Check power supply to
to other outdoor units for at
outdoor units. (Is power
least 30 seconds
turned on?)
continuously.
• Check connection of tie
cables between outdoor
units for bad contact or
broken wire.
• Check communication
connectors on outdoor
P.C. boards.
• Check for defect in outdoor
P.C. board (I/F).
• Check termination
resistance setting for
communication between
outdoor units.
There is duplication in
Note:
outdoor addresses set
Do not set outdoor
manually.
addresses manually.
Outdoor unit initially
• Backup setting is being
communicating normally fails
used for outdoor units.
to return signal for specified
• Check power supply to
length of time.
outdoor unit. (Is power
turned on?)
• Check connection of tie
cables between outdoor
units for bad contact or
broken wire.
• Check communication
connectors on outdoor
P.C. boards.
• Check for trouble in outdoor
P.C. board (I/F).
Outdoor header unit receives
• Check check code
check code from outdoor
displayed on outdoor
follower unit.
follower unit.
<Convenient functions>
If SW04 is pressed and held
for at least 1 second while
[E28] is displayed on the 7-
segment display of outdoor
header unit, the fan of the
outdoor unit that has been
shut down due to a trouble
comes on.
If SW04 and SW05 are
pressed simultaneously, the
fans of normal outdoor units
come on.
To stop the fan or fans,
press SW05 on its own.