Toshiba MMY-MAP1006FT8(J)P-E Service Manual page 72

Super heat recovery multi-e (multi type) outdoor unit
Hide thumbs Also See for MMY-MAP1006FT8(J)P-E:
Table of Contents

Advertisement

NO.
Item
14 Filter sign
1. The indoor fan's cumulative hours of operation are counted, and when these
display
exceed the prescribed value (150H/2500H), a filter replacement signal is sent to
(not applicable
the remote controller to display a filter sign on it.
to wireless type)
2. When a filter reset signal is received from the remote controller, the timer
* Provided in
measuring cumulative hours is cleared. If the prescribed hours have been
the separately
exceeded, the hours count is reset, with the sign on the remote controller display
mounted type,
erased.
TCB-AX21E.
15 Operation
<Operation standby> .......... Displayed on remote controller
standby
1. When any of the DN codes listed below is displayed
Heating
• "P05" - Detection of an open phase in the power supply wiring
standby
• "P10" - Detection of indoor flooding in at least one indoor unit
• "L30" - Detection of an interlock alarm in at least one indoor unit
2. All indoor units not able to engage in any of the above operations stand by in
thermostat OFF state.
3. The indoor fan has been turned off because the system is engaged in a heat
refrigerant (oil) recovery operation.
<Heating standby> .......... Displayed on remote controller
1. Normal thermostat OFF
• During heating, the indoor unit goes thermostat OFF as the heating
2. During heating, the fan rotates at a breeze speed (UL or lower) or remains
stationary to prevent cold air from being discharged (including defrosting
operation).
3. Forced thermostat OFF
• "HEAT" operation is unavailable because at least one indoor unit is operating in
16 Selection of
1. The range of operations that can be performed via an indoor unit remote controller
central control
can be determined through the setting of the central controller.
mode
2. Setting details
TCC-Link central control
Link central
(
Specification outline
Filter service life
4-way cassette type
1-way cassette type
(SH, YH)
2-way cassette type ceiling type
Type
Concealed duct standard type
Concealed duct high static
pressure type
Slim duct type
temperature setting is reached.
"COOL/DRY" mode under priority cooling setting (bit 1 of SW11 on outdoor I/F
P.C. board ON).
Operation via RBC-AMT32E
Operation
via TCC-
Operation
Start/stop
mode
selection
control
selection
Individual
Central 1
Central 2
Central 3
Central 4
: Accessible
: Inaccessible)
2500H
High wall type
Floor standing type
Floor standing concealed
type
Floor standing cabinet type
Timer
Temperature
Fan speed
direction
setting
setting
setting
– 71 –
"FILTER
150H
• "OPERATION
• "HEATING
• In the case of a
RBC-
Air flow
AMT32E
display
setting
• The display blinks
"CENTRAL
CONTROL
IN
PROGRESS"
• A wireless remote
Remarks
" displayed
STANDBY
"
displayed
No display
provided on
wireless remote
controller
STANDBY
"
displayed
wired remote
controller,
"CENTRAL
CONTROL IN
PROGRESS
"
is displayed (lit
up) while in
central control
mode.
when a control
function
inaccessible to a
remote controller
is chosen.
controller has the
same set of
control functions,
although there is
no display.
When a control
operation is
performed via a
wireless remote
controller while in
central control
mode,
a peep sound
alert (5 times) is
provided.